2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 SHOWING DETAIL/BREAKDOWN OF CALCS.
 YOU HAVE NOTE ON PLAN FOR CONTINUOUS
 LOADS? PLEASE SHOW IT IN THE CALCULATION
 FOR ALL CONTINUOUS LOADS. (LIGHTING ETC)
  
 2)NOTE: PLEASE NOTE THAT THE MDP NEEDS
 TO CORRELATE WITH THE LOADS SHOWN ON
 PANELS. PLEASE MATCH UP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH A
 PROVISO, BUT WERE COMING BACK FOR PLUMB
 COMMENTS. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372