| Plan Review Notes For Permit 00050833 |
| Permit Number |
00050833 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | SHOWING DETAIL/BREAKDOWN OF CALCS. | | | YOU HAVE NOTE ON PLAN FOR CONTINUOUS | | | LOADS? PLEASE SHOW IT IN THE CALCULATION | | | FOR ALL CONTINUOUS LOADS. (LIGHTING ETC) | | | | | | 2)NOTE: PLEASE NOTE THAT THE MDP NEEDS | | | TO CORRELATE WITH THE LOADS SHOWN ON | | | PANELS. PLEASE MATCH UP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLANS WOULD HAVE PASSED WITH A | | | PROVISO, BUT WERE COMING BACK FOR PLUMB | | | COMMENTS. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|