| Plan Review Notes For Permit 00050759 |
| Permit Number |
00050759 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE:PLANS ARE SUBMITTED SHOWING AN | | | ELECTRIC POOL HEATER ,YET SPEC SHEET | | | SHOWS IT AS BEING GAS??? | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR EXISTING SERVICE AND LOAD OF NEW | | | HEATER. SHOW THE EXISTING SERVICE SIZE. | | | 215-5 | | | | | | 3)NOTE: THE ELECTRICAL DRAWING SHOWS | | | 3 #12`S GOING TO HEATER? PLEASE SHOW | | | CORRECT WIRING METHOD TO POOL HEAT. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|