Plan Review Notes
Plan Review Notes For Permit 00050759
Permit Number 00050759
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE:PLANS ARE SUBMITTED SHOWING AN
 ELECTRIC POOL HEATER ,YET SPEC SHEET
 SHOWS IT AS BEING GAS???
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING SERVICE AND LOAD OF NEW
 HEATER. SHOW THE EXISTING SERVICE SIZE.
 215-5
  
 3)NOTE: THE ELECTRICAL DRAWING SHOWS
 3 #12`S GOING TO HEATER? PLEASE SHOW
 CORRECT WIRING METHOD TO POOL HEAT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372