| Plan Review Notes For Permit 00050758 |
| Permit Number |
00050758 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLANS SUBMITTED ARE SHOWING | | | ELECTRICAL HEATER? CONTRACT IS SHOWING | | | GAS? WHICH IS IT? | | | | | | 2)NOTE: IF ELECTRIC, NEED TO SUBMIT LOAD | | | CALCULATIONS FOR EXISTING SERVICE AND | | | LOAD BEING ADDED BY ELEC. HEATER. | | | SHOW EXISTING SERVICE SIZE.215-5 | | | | | | | | | 3)NOTE: ALSO, YOU ARE SHOWING 3#12`S | | | GOING TO POOL HEATER? PLEASE SHOWTHE | | | CORRECT WIRING METHOD.215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW. IF THERE AREANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|