| 2001-01-08 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS OF |
| | THE MAIN AND BRKRS. AS REQ`D BY 215-5 |
| | AND 110-9. AIC RATINGS CAN BE FIGURED |
| | FROM FAULT CURRENT CALCULATIONS. |
| | |
| | 2)NOTE: UPSTAIRS OUTLET SPACING TO MEET |
| | CODE. 210-52 AND ALL OUTLET SPACING TO |
| | BE BROUGHT UP TO CODE. MORE THAN 50% |
| | OF THE ELECTRICAL WORK IS BEING DONE. |
| | |
| | 3)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. PLEASE SHOW ON PLANS. |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AND ON |
| | EACH LEVEL OF THE DWELLING.THEY ALL MUST |
| | BE WIRED INLINEAND 120V W/BATT BACK |
| | UP. |
| | |
| | |
| | 5)NOTE PLEASE SHOW THE EQUIPMENT GROUND- |
| | ING CONDUCTORS REQ`D FOR CONDUITS TO A/C |
| | UNITS. |
| | |
| | 6)NOTE; PLEASE INCLUDE COLD WATER PIPE |
| | AS PART OF THE GROUNDING ELECTRODE SYS-E |
| | -TEM. 250-50 |
| | |
| | 7)NOTE: AS REQ`D BY 210-11-C-3 PLEASE |
| | SHOW THE REQ`D DEDICATED BATH(S)CIRCUITS |
| | MUST BE #12 AND 20 AMPS. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |