Plan Review Notes
Plan Review Notes For Permit 00050756
Permit Number 00050756
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS OF
 THE MAIN AND BRKRS. AS REQ`D BY 215-5
 AND 110-9. AIC RATINGS CAN BE FIGURED
 FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: UPSTAIRS OUTLET SPACING TO MEET
 CODE. 210-52 AND ALL OUTLET SPACING TO
 BE BROUGHT UP TO CODE. MORE THAN 50%
 OF THE ELECTRICAL WORK IS BEING DONE.
  
 3)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW ON PLANS.
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND ON
 EACH LEVEL OF THE DWELLING.THEY ALL MUST
 BE WIRED INLINEAND 120V W/BATT BACK
 UP.
  
  
 5)NOTE PLEASE SHOW THE EQUIPMENT GROUND-
 ING CONDUCTORS REQ`D FOR CONDUITS TO A/C
 UNITS.
  
 6)NOTE; PLEASE INCLUDE COLD WATER PIPE
 AS PART OF THE GROUNDING ELECTRODE SYS-E
 -TEM. 250-50
  
 7)NOTE: AS REQ`D BY 210-11-C-3 PLEASE
 SHOW THE REQ`D DEDICATED BATH(S)CIRCUITS
 MUST BE #12 AND 20 AMPS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372