2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:NEED TO SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANLE SCHEDULE.
 210-11-C-3/ 215-5
  
 2)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 AS PART OF THE GROUNDING ELECTRODE
 AS REQ`D BY 250-50
  
 3)NOTE: PLEASE CORRECT THE WIRE SIZES
 FOR THE SERVICE CONDUCTORS. SIZE PER
 310-16.YOU SHOW #1,NEEDS TO BE INCREASED
  
  
 4)NOTE;PLEASE PROVIDE THE AIC RATING FOR
 THE EQUIPMENT MAINS. MAINS TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
  
 5)NOTE:PLEASE NOTE YOU SHOW THE LIGHTING
 IN THE CLOSETS AS (PC)`S PULL CHIANS?
 SEE ART 410-8 FOR CLEARENCEREQ`MENTS
 PLEASE CHANGE LIGHTING SHOWN ON PLANS.
  
 6)NOTE:PLEASE NOTE THAT THE GUARDRAIL
 SHOWN ON SECOND FLOOR GUEST SUITE IS
 CONSIDERED WALL SPACE. OUTLET SPACING
 PER 210-52 MUST BE MET. FLOOR BOXES? ETC
  
 7)NOTE: NO DOORSARE BEING SHOWN ON
 ANY OF THE BEDROOMS?/BATHS? AND ALSO
 FROM UPSTAIRS TO DOWNSTAIRS? PLEASE GIVE
 MORE DETAIL FOR ANY INTERIOR DOORS.
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AND ON EACH
 FLOOR LEVEL AT COMMON AREA. NFPA-72
 2-2.1.1.1. NEED TO SEE WHAT DOORS IF ANY
 ARE BEING INSTALLED.
  
 8)NOTE: YOU ARE ALSO SHOWING TWO A/C
 UNITS? ARE THEY BOTH EXISTING? IF NOT
 PLEASE SHOW ONPLANS THE NEW A/C`S AND
 SHOW THE REQ`DE A/C DISCS AND REQ`D
 210 RECEPT. 440-11 AND 210-63
  
 9)NOTE: YOU ARE SHOWING A TELEPHONE
 IN THE MASTER SUITE, IS THERE GOING TO
 BE ONE IN THE GUEST SUITE?OR IN KITCHEN?
 NEED SHOW ANY CABLE TV OUTLETS THAT ARE
 GOING TO BE INSTALLED,IF ANY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372