| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL EXISTING ELEC- |
| | -TRIC IN EXISTING ROOMS. SEEING THAT |
| | MORE THAN 50% OF THE ELECTRICAL WORK |
| | IS BEING DONE, ELECTRICAL NEEDS TO BE |
| | BROUGHT UP TO CODE. |
| | |
| | 2)NOTE; PLEASE INDICATE ON PLANS ALL |
| | EXISTING ELECTRIC THAT IS INSTALLED IN |
| | THE EXISTING ROOMS. |
| | |
| | 3)NOTE: SMOKE DETECTORS WILL BE REQ`D |
| | INSDIE AND OUTSIDE ALL SLEEPING ROOMS. |
| | AS PER NFPA -72 2-2.1.1.1 |
| | |
| | 4)NOTE; MISSSING MEANS OF EGRESS LIGHT- |
| | ING OUTSIDE EXISTING FAMILY ROOM.210-70 |
| | |
| | 5)NOTE:PLEASE NOTE THE MISSING GFI OUT- |
| | -LET REQ`D FOR A/C UNIT. PER 210-63 |
| | |
| | 6)NOTE:PLEASE NOTE THAT ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. PLEASE SHOW.MISSING |
| | ONE. |
| | |
| | 7)NOTE;AS REQ`D BY 220-3-C-1 NEED TO |
| | SUBMIT COMPLETE LOAD CALCULATION FOR |
| | EXISTING AND ALL NEW LOADS. 215-5 |
| | PLEASE SHOW EXISTING SERVICE SIZE TO |
| | INCLUDE RISER DIAGRAM WITH ALL WIRE |
| | SIZES,CONDUITS, GROUNDING SYSTEM. |
| | IF NEW SERVICE PLEASE INDICATE ON PLANS. |
| | |
| | |
| | 8)NOTE: PLEASE PROVIDE NEW PANEL SSCHED- |
| | -ULE FOR NEW CIRCUITS. PLEASE INCLUDE |
| | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) |
| | AS PER 210-11-C-3. NEEDS TO BE #12 AND |
| | 20 AMP. |
| | |
| | 9)NOTE: YOU ARE SHOWING ALL THE NEW |
| | TELEPHONE OUTLETS,WHAT ABOUT TV? IF YOU |
| | ARE GOING TO HAVE CABLE TV OUTLETS THEN |
| | PLEASE SHOE ON PLANS. |
| | |
| | 10)NOTE: PLEASE NOTE THAT ALL EXISTING |
| | AND NEW OUTLET SPACING WILL HAVE TO BE |
| | BROUGHT UP TO CODE AND MEET 210-52. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS |
| | PLEASECALL 659-8096 EXT 8372 |