Plan Review Notes
Plan Review Notes For Permit 00050450
Permit Number 00050450
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 NOT ENOUGH ELECTRIACL INFORMATIN FOR
 PLAN REVIEW!!!
  
 1)NOTE: PLEASE SHOW EXISTING ELECTRICAL!
 PLEASE INCLUDE EXISTING LIGHTING,OUTLETS
 AND SERVICE.
  
 2)NOTE: YOU ARE SHOWINGNO ELECTRICAL
 OUTLETS. OUTLET SPACING FOR ALL AREAS
 MUST MEET LOCAL CODE INCLUDING STOCK
 AREA. PER 210-50 OF THE PALM BEACH
 COUNTY AMENDMENTS.
  
 3)NOTE: YOU SHOW NEW CABINET FOR CHECK-
 OUT STATION? IS THERE ANY ELECTRICAL
 FOR THIS? IF SO PLEASE SHOW.
  
 4)NOTE: PLEASE SHOW ANY OUTLETS REQ`D BY
 210-62 FOR SHOW WINDOWS.
  
 5)NOTE: PLANS SHOW SIGNAGE BEING INSTALL
 -ED? IF SO IS THERE ELECTRICAL TO SIGN?
  
 PLEASE SUBMIT A MORE DETAILED PLAN FOR
 REVIEW WITH ALL THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL\\
 659-8096 EXT 8372