Plan Review Notes For Permit 00050442
Permit Number 00050442
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SANITARY PIPING DIAGRAM THAT
 CLEARLY REFLECTS THE SCOPE OF WORK BEING
 PERFORMED.COUNTYWIDE AMENDMENTS TO SPC
 SEC.102.4.1,717.11.
  
 EJECTORS SHALL BE VENTED PER 714.4,717.6
  
 A CHECK VALVE AND GATE VALVE ARE REQD.
 ON THE PUMP /EJECTOR PER SPC 717.2.
  
 AIR ADMITTANCE VALVES SHALL NOT BE USED
 TO RELIEVE POSITIVE PRESSURE PER SPC SEC
 905.7.5 AND MANUFACTURER'S RECOMMEN-
 DATIONS.
  
 PIPING CONNECTION FROM EJECTORS TO
 BUILDING DRAINAGE SYSTEM SHALL COMPLY W/
 SPC SEC.717.11.