| Plan Review Notes For Permit 00050442 |
| Permit Number |
00050442 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SANITARY PIPING DIAGRAM THAT | | | CLEARLY REFLECTS THE SCOPE OF WORK BEING | | | PERFORMED.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.102.4.1,717.11. | | | | | | EJECTORS SHALL BE VENTED PER 714.4,717.6 | | | | | | A CHECK VALVE AND GATE VALVE ARE REQD. | | | ON THE PUMP /EJECTOR PER SPC 717.2. | | | | | | AIR ADMITTANCE VALVES SHALL NOT BE USED | | | TO RELIEVE POSITIVE PRESSURE PER SPC SEC | | | 905.7.5 AND MANUFACTURER'S RECOMMEN- | | | DATIONS. | | | | | | PIPING CONNECTION FROM EJECTORS TO | | | BUILDING DRAINAGE SYSTEM SHALL COMPLY W/ | | | SPC SEC.717.11. |
|