Plan Review Notes
Plan Review Notes For Permit 00050421
Permit Number 00050421
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO **************
  
 1)NOTE:PLEASE SHOW LOCATION OF PANELS
 ON FLOOR POWER SHEET.215-55
  
 2)NOTE: PLEASE SUBMIT THE AIC RATING OF
 THE MAIN FOR 850. PER 110-9/215-5
 YOU SHOW PANEL RATING, BUT NOT THE
 RATING FOR THE MAIN DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT-
 8372