| Plan Review Notes For Permit 00050421 |
| Permit Number |
00050421 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO ************** | | | | | | 1)NOTE:PLEASE SHOW LOCATION OF PANELS | | | ON FLOOR POWER SHEET.215-55 | | | | | | 2)NOTE: PLEASE SUBMIT THE AIC RATING OF | | | THE MAIN FOR 850. PER 110-9/215-5 | | | YOU SHOW PANEL RATING, BUT NOT THE | | | RATING FOR THE MAIN DISCONNECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT- | | | 8372 |
|