| Plan Review Notes For Permit 00050295 |
| Permit Number |
00050295 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 5/9/00 PLANS DENIED, SEE FOLLOWING | | | | | | 1. LETTER FROM SPECIAL INSPECTOR | | | RELEASING THE SPACE FOR CONSTRUCTION. | | | 2. FLORIDA ENERGY SHEETS OK 6/15/00 | | | 3. FIRE SPRINKLER APPREC 6/15/00MIT | | | 4. EXTERIOR GLAZING TO MEET 1997 SBC FOR | | | IMPACT PROTEOK REC 6/15/00 LOADS. | | | 5. SHEET A5.1 EIFS SHALL MEET THE | | | REQUIREMENTS OF 1997 SBC CHAPTER 26 AND | | | PROVIDE PRODUCT APPROVAL INFORMATION. | | | 6. SIGNS REQUIRE SEPERATE PERMITS. | | | 7. SHEET 10.1 REVISE LOCATION ADDRESS TO | | | PROPER NUMBER A11 IS NOT APPROVED. | | | 8. SHEET A2.1 SECTION 3 ON A6.3 SHOULD | | | BE A WALL SECTION DRAWING IS A CELING | | | DETAIL? | | | 9. SHEET A2.1 SECTION 3 ON A6.5 SHOULD | | | BE A WALL SECTION DETAIL IS FOR A CARPET | | | TO WOOD SITUATION? | | | SHEET A2.1 SECTION 7 ON A6.5 SHOULD BE A | | | STRUCTURAL SECTION FOR A NEW DOOR DETAIL | | | IS FOR THE DOOR THRESHOLD? | | | 10. SHEET A6.1 DETAIL J SECTION 1 ON | | | A-6.2 FOR FIRE SEPERATION IS A CROSS | | | BRACING DETAIL? | | | 11. PLAN REVIEW STOPPED, REVIEW ALL | | | DRAWING AND RE SUBMIT AFTER COORDINATION | | | OF CONSTRUCTION DETAILS. |
|