| Plan Review Notes For Permit 00050266 |
| Permit Number |
00050266 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1. DRYER VENT TO BE SHOWN ON PLANS. | | | 2. RETURN AIR TO BE INDICATED. | | | 3. EXHAUST FANS TO BE SHOWN AND INSTALL | | | IN BATHROOMS. | | | 4. PLANS SHOW A TOTAL OF 1738 CFM'S | | | A/C SUPPLY OF 1400 CFM'S | | | A/C UNIT TOO SMALL FOR THE DEMAND. | | | 5. ENERGY CALCULATIONS REQUIRED. |
|