| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT THE AIC RATING OF |
| | EQUIPMENT MAIN. MAINS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT.110-9/215-5 |
| | THIS IS REQ`D ON ALL PLANS. |
| | |
| | 2)NOTE: PLEASE INCLUDE THE COLD WATER |
| | PIPE AND BLDG.STEEL AS PART OF THE |
| | GROUNDING ELETRODE SYSTEM,AS PER 250-50 |
| | |
| | 3)NOTE: PLEASE INDICATE THE PANEL AS \\ |
| | BEING MAIN BRKR 215-5 |
| | |
| | 4)NOTE: PLEASE SHOW THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210-11-C-3 |
| | |
| | 5)NOTE: PLEASE SEE THE MISSING OUTLET |
| | REQ`D FOR TWO FEET OF WALL 210-52. |
| | |
| | 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | ARE REQ`DOUTSIDE ALL SLEEPING ROOMS |
| | IN NEW DWELLINGS. NFPA-72 2-2.1.1.1 |
| | |
| | 7)NOTE:PLEASE COMPLETE LOAD CALCULATION. |
| | |
| | 8)NOTE:PLEASE SEE PANEL SCHEDULE.YOU |
| | SHOW 4500VAON 20AMPTHIS MUST BE |
| | RATED AT 125% OF MIN CIRCUIT AMPACITY, |
| | |
| | |
| | 9)NOTE: PLEASE SHOW THE SWITCH LOCATION |
| | FOR EGRESS LIGHTING IN GARAGE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |