2001-05-22 00:00:00TRUSS DRAWINGS SECOND CHECKLIST:
  
 1-TRUSS LAYOUT AND ENGINEERED TRUSSES:
 A)WHO IS THE ENGINEER RESPONSIBLE FOR
 THE LAYOUT? MISSING INFORMATION AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 (NO DONE FROM PREVIOUS CHECKLIST).
  
 B)WHY IS THERE ANOTHER ENGINEER SIGNING
 AND SEALING THE ENGINEERED TRUSSES?
 C)WHY IS THERE ANOTHER ENGINEER SIGNING
 AND SEALING THE PARALLAM BEAM?
 D)WHERE IS TRUSS FGA ON TRUSS LAYOUT?
 E)ENGINEER TO PROVIDE ORIGINAL
 SIGNATURE ON TRUSS FGA AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 F)UPDATE DESIGN CRITERIA ON TRUSS
 LAYOUT AS REQUIRED: ASCE 7-95 145MPH
 (NO DONE FROM PREVIOUS CHECKLIST).
  
 2-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 -USE STANDARD REVIEW STAMP TO IDENTIFY
 REVIEWED DRAWINGS.
  
 3-ARCHITECT TO PROVIDE A COMPLETE ANCHOR
 SCHEDULE THAT IS CLEARLY KEYED TO THE
 FRAMING PLANS.INFORMATION SUBMITTED
 IS VERY CONFUSING AND IS NOT CLEAR
 WHERE IT APPLIES TO.
  
  
 NOTE: INFORMATION SUBMITTED IS VERY
 CONFUSING & RAISES MORE QUESTIONS
 THAN ANSWERS. IF YOU HAVE ANY
 QUESTIONS CONCERNING MY COMMENTS,
 PLEASE CALL JULIO GOMEZ AT
 659-8096 EXT. 8232.