Plan Review Notes
Plan Review Notes For Permit 00050265
Permit Number 00050265
Review Stop R
Sequence Number 3
Notes
Date Text
2001-05-07 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-WHO IS THE ENGINEER FOR THE TRUSS
 DRAWINGS? IT IS MISSING ALL THE
 INFORMATION REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.
 2-PROVIDE TWO COPIES OF THE ENGINEERED
 TRUSSES USING ASCE 7-95 FOR 145 MPH
 (NOT ASCE FOR 110 MPH AS SHOWN ON
 TRUSS LAYOUT).
 3-ARCHITECT OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
 4-ARCHITECT TO PROVIDE A COMPLETE ANCHOR
 SCHEDULE SPECIFYING CONNECTORS TO
 RESIST CALCULATED LOADS ON ENGINEERED
 DRAWINGS.
 5-UPDATE TRUSS LAYOUT DESIGN CRITERIA.
 SEE COMMENTS ON LAYOUT.