Plan Review Notes
Plan Review Notes For Permit 00050265
Permit Number 00050265
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR NEW LOAD AND EXISTING LOADS REQ`D BY
 220-3-C-1 PLEASE SHOW EXISTING SERVICE
 SIZE. RISER DIAGRAM.
  
 2))NOTE: PLEASE NOTE THAT SMOKE DETECTOR
 -S ARE REQ`D INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS IN NEW DWELLINGS/ AREAS.
 NFPA-72 2-2.1.1.1
  
 3)NOTE:PLEASE LIST ON THE PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-11-C-3 MUST BE 20AMP #12 AWG.
  
 4)NOTE: PLEASE SEE MISSING OUTLET PER
 210-52 2` OF WALL.
  
 5)NOTE:PLEASE LABEL ALL GFI RECEPTS IN
 GARAGE AS BEING GFI/GFI PROTRECTED AS
 REQ`D BY 210-8/215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASECALL 659-8096 EXY 8372