| Plan Review Notes For Permit 00050265 |
| Permit Number |
00050265 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | FOR NEW LOAD AND EXISTING LOADS REQ`D BY | | | 220-3-C-1 PLEASE SHOW EXISTING SERVICE | | | SIZE. RISER DIAGRAM. | | | | | | 2))NOTE: PLEASE NOTE THAT SMOKE DETECTOR | | | -S ARE REQ`D INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS IN NEW DWELLINGS/ AREAS. | | | NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE:PLEASE LIST ON THE PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | | PER 210-11-C-3 MUST BE 20AMP #12 AWG. | | | | | | 4)NOTE: PLEASE SEE MISSING OUTLET PER | | | 210-52 2` OF WALL. | | | | | | 5)NOTE:PLEASE LABEL ALL GFI RECEPTS IN | | | GARAGE AS BEING GFI/GFI PROTRECTED AS | | | REQ`D BY 210-8/215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASECALL 659-8096 EXY 8372 |
|