| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST TWO | | | REVIEWS. | | | | | | 2)NOTE: PLEASE SEE PANELS "B" AND "C" | | | STILL SHOW (3) AIR HANDLER UNIT #1. | | | ALSO WIRE SIZED AT 10AWG W/ 50A, 10KW | | | LOAD.? | | | | | | 3)NOTE: PLEASE SEE BRKR FEED TO PANEL | | | "C". SHOWN AT 2P30? 1/0 CONDUCTOR SIZE.? | | | | | | 4)NOTE: PLEASE NOTE THAT AIC RATINGS FOR | | | PANELS HAVE NOT BEEN SUBMITTED. | | | PER110-9 AND 215-5 | | | | | | 5)NOTE: PANEL SCHEDULES FOR PANEL "A" | | | SHOWS MLO?? WHERES MAIN? | | | S | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|