Plan Review Notes
Plan Review Notes For Permit 00050235
Permit Number 00050235
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST TWO
 REVIEWS.
  
 2)NOTE: PLEASE SEE PANELS "B" AND "C"
 STILL SHOW (3) AIR HANDLER UNIT #1.
 ALSO WIRE SIZED AT 10AWG W/ 50A, 10KW
 LOAD.?
  
 3)NOTE: PLEASE SEE BRKR FEED TO PANEL
 "C". SHOWN AT 2P30? 1/0 CONDUCTOR SIZE.?
  
 4)NOTE: PLEASE NOTE THAT AIC RATINGS FOR
 PANELS HAVE NOT BEEN SUBMITTED.
 PER110-9 AND 215-5
  
 5)NOTE: PANEL SCHEDULES FOR PANEL "A"
 SHOWS MLO?? WHERES MAIN?
 S
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372