Plan Review Notes
Plan Review Notes For Permit 00050235
Permit Number 00050235
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 THE EQUIPMENT MAINS. MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT AS REQ`D BY
 110-9 AND 215-5.
  
 2)NOTE; PLEASE NOTE THAT ON THE PANEL
 SCHEDULES YOU ARE SHOWING GAS WATER
 HEATER AND GAS DRYER AND YET YOU ARE
 SHOWING A HIGH ELECTRIC LOAD. ?? PLEASE
 CALRIFY.IF GAS PLEASE CORRECT LOAD.
  
 3) NOTE: PLEASE NOTE AS REQ`D BY 210-11-
 -C-3 . PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) . MUST BE 20 AMP AND
 #12 AWG.
  
 4)NOTE: PLEASE CORRECT LOAD SHOWN FOR
 ELECTRIC COOK TOP? 2000VA 2P50?
  
 5)NOTE: YOU SHOW TWO AHU-1 PLEASE CORREC
 -T. AND NOTE THAT YOU ARE SHOWING 10000W
 ON #10 AWG.2P50.
  
 6)NOTE:MISSING OUTLET SECOND FLOOR 2`OF
 WALL 210-52
  
 7)NOTE: PLEASE NOTE SD MISSING SD OUT-
 -SIDE BEDROOM. UPSTAIRS AND NEED TO
 MOVE SD DOWNSTAIRS TO BE IN THE VICINITY
 OF STAIRS. NFPA-72 2-2.1.1.1
  
 8)NOTE:PLEASE INCLUDE AND SHOW THE COLD
 WATER PIPE AND BLDG.STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AND SHOW ON
 RISER DIAGRAM. 250-50 /215-5
  
 9)NOTE:PLEASE LABEL AND SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED AS REQ`D BY 210-8-A-6.
  
 10)NOTE: PLEASE NOTE MISSING OUTLET REQ`
 FOR COUNTER OUTLET SPACING PER 210-52-
 C-1.
  
 11)NOTE:MISSING SMOKE DETECTOR OUTSIDE
 BEDROOM DOWNSTAIRS.
  
 12)NOTE: MISSING MEANS OF EGRESS LIGHT-
 -ING OUTSIDE GARAGE DOOR. 210-70
  
 13)NOTE:MISSING GFI REC FOR A/C CU`S
  
 14)NOTE: PLEASE SHOW PANEL LOCATIONS ON
 FLOOR PLAN., 215-5
  
 15)NOTE:MISSING OUTLETS FOR 2` OF WALL
 FOYER/DEN
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH/ELEC FOR SLAB.
 THIS INFORMATION MUST BE PROVIDED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372