| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO *************** | | | | | | 1)NOTE: PLEASE SUBMIT NEW REVISED PANEL | | | SCHEDULE. | | | | | | 2)NOTE: REVISE PLANS TO SHOW NEW SMOKE | | | DETECTORS REQ`D INSIDE AND OUTSIDE | | | BEDROOMS. NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: NEED TO SHOW THE REQ`D BATH(S) | | | CIRCUITS PER 210-11-C-3 ON PANEL SCHED. | | | | | | 4)NOTE;PLEASE SEE THE REQ`MENTS FOR | | | 410-4-D ADN 410-8 FOR LIGHTING. | | | YOU ARE SHOWING LIGHTING IN CLOSETS?THIS | | | IS OK BUT NEED TO CHECK ON TYPE OF FIX- | | | -TURES AND CLEARENCE\\ | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL IS | | | CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|