| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE ART 210-62 OF THE NEC | | | AS TO THE REQ`MENTS FOR SHOW WINDOW | | | OUTLETS. | | | | | | 2)NOTE:YOU ARE SHOWINGEXISTING BUILD. | | | SERVICE BEINGREFED BY SERVICE ON NEW | | | BUILD. THE EXISTING BUILDING MUST BE | | | PART OF THE NEW BUILDING.THIS MEANS | | | STRUCTUALLY ATTACHED AND BY ZONING | | | APPROVAL. IF THIS IS THE CASE THEN | | | PLEASE HAVE SERVICE CLEARLY LABELED AS | | | TO WHAT THE MAINS DISCONNECTS. | | | | | | 3)NOTE: PLEASE SUBMIT ALL AIC RATINGS | | | OF MAINS AND PANELS. PER 110-9 AND 215-5 | | | MAINS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. | | | | | | 4)NOTE:ALL LOAD CALCUALTIONS NEED TO | | | SHOW ALL CONTINUOUS LOADS FIGURED AT | | | 125%. PLEASE SHOW.LIGHTING ETC. | | | | | | 5)NOTE: PANEL SCHEDULE/OR PLANS DO NOT | | | SHOW THE REQ`D ROOFTOP RECEPT. REQ`D BY | | | 210-63 PLEASE SHOW | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|