| Plan Review Notes For Permit 00050057 |
| Permit Number |
00050057 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | *FAN SHUTDOWN FOR A SYSTEM UNDER | | | 2000 CFM SERVING AN AREA USED AS AN | | | EGRESS AS PER 1997 SMC 406.2.... | | | *ADDITIONAL PERMIT REQUIRED FOR HOOD, | | | FIRE SUPPRESSION SYSTEM, FUEL AND WALK- | | | IN COOLER/FREEZER. | | | | | | ***EXHAUST DUCT INSIDE RATED SHAFT SHALL | | | MAINTAIN A MINIMUM CLEARANCE OF 6" AS | | | PER 1997 SMC 505.9.1 AND NOT AS STATED | | | ON SHEET M7 OF THE PLANS. |
|