| Plan Review Notes For Permit 00050057 |
| Permit Number |
00050057 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT***************** | | | | | | 1)NOTE: UNSAT FOR PHASE TWO (II) | | | PLEASE SEE AND ADDRESS FIRST SET OF | | | NOTES GIVEN BY JAKE LEAHY. | | | | | | 2)NOTE: PLEASE PROVIDE CONDUIT LAYOUT | | | PLAN, SHOWING CONDUIT SIZES FOR PHASE | | | I ONLY. | | | | | | 3)NOTE: PLEASE SUBMIT SPECS ON 1400 AMP | | | OCP SHOWN AT 1600AMP MAIN. 1400 AMP | | | FUSES ARE NOT STANDARD AND IF YOU HAVE | | | A MANUFACTURE`S LISTING, THEN PLEASE | | | SUBMIT. SEE ART;240-6 | | | | | | | | | IF WIRE SIZES, AND CONDUIT SIZES CHANGE | | | DUE TO MAIN OCP THEN THERE WOULD BE A | | | PROBLEM ISSUING ANY PERMIT FOR PHASE I | | | ELECTRICAL. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|