Plan Review Notes
Plan Review Notes For Permit 00050057
Permit Number 00050057
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00JOB SPECIFICATION 15000-SEC.1.04-THE
 PLUMBING CODE IN EFFECT IS THE 1994
 EDITION OF THE STANDARD PLUMBING CODE.
 REVISE THE SPECS.TO REFLECT THIS STAN-
 DARD.
  
 SUBMIT OCCUPANT LOAD OF EACH AREA PER
 SPC TABLE 407 FOR DETERMINATION OF MIN.
 REQUIRED SANITARY FACILITIES.SEE SEC.
 407.1.3. FOR ALLOWED DEDUCTIBLE AREAS.
  
 DELETE REFERENCE TO THE UNIFORM BUILDING
 CODES NOTED THROUGHOUT THE PLANS.THE
 STANDARD BUILDING CODES ARE THE ADOPTED
 STANDARDS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.1.
  
 SUBMIT A COMPLETE SANITARY AND WATER
 ISOMETRIC FOR REVIEW.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 SUBMIT A GAS ISOMETRIC FOR REVIEW.SHOW
 DISTANCE TO MOST REMOTE OUTLET,PIPE
 SIZES,TYPE OF PIPING,TYPE OF GAS,BTU
 LOAD OF EACH APPLIANCE,TOTAL BTU LOAD ON
 THE SYSTEM,TYPE OF VENT,ETC.SGC SEC.302.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/SGC SEC.402.4.
  
 DRAINS FROM THE BAR AREA SHALL DISCHARGE
 THROUGH THE GREASE INTERCEPTOR PER SPC
 SEC.1004.4.
  
 DRAINS IN BAR AND KITCHEN AREAS SHALL
 DISCHARGE TO THE BUILDING DRAINAGE SYS-
 TEM THROUGH AN INDIRECT WASTE PER SPC
 SEC.804.INSTALLATION OF INDIRECT WASTES
 SHALL COMPLY W/SPC SEC.805.1,806,807.
  
 CAPACITY OF GREASE TRAP SHALL BE
 APPROVED BY CITY OF WPB UTILITIES.SUBMIT
 APPROVAL FORM FROM CITY OF WPB.CONTACT
 R.COMPO AT(561)835-7423.
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET TO THE GREASE TRAP PER SPC
 SEC.710.4.
  
 SUPPLY MANUF.INSTALLATION INSTRUCTIONS
 FOR POWER VENT INSTALLATION.COMPLY W/
 SGC SEC.610.3.
  
 BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/VACUUM RELIEF VALVE PER SPC
 SEC.507.1.2.
  
 NUMBER OF SANITARY FACILITIES SHALL
 COMPLY W/FLA.STATUTE 553.141(1)(2)(3).