| Plan Review Notes For Permit 00050057 |
| Permit Number |
00050057 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-PG. E-5 MAIN FEEDER TO MDP IS TOO SMAL | | | WIRE HAS TO MATCH BREAKER AND BE BASED | | | ON 75C RATING NOT 90C 110-14(C2) | | | | | | 2-PG. E-5 GROUNDING ELECTRODE CONDUCTOR | | | IS TOO SMALL SHOULD BE A LEAST A 4/0 | | | 250-66 | | | | | | 3-PG. E-5 NO AIC RATINGS SHOWN FOR ANY | | | PANELS, MAINS, BREAKERS, OR OTHER EQUP | | | 110-9,10 |
|