| Plan Review Notes For Permit 00050057 |
| Permit Number |
00050057 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***PLAN REVIEW COMMENTS*** | | | | | | 1]SIGNED AND SEALED SURVEYS ARE REQUIRED | | | 2]PROVIDE CITY'S APPROVAL FOR CONSTR. | | | ON CITY PROPERTY. | | | 3]SUBMIT TEST REPORTS FOR ALL INTERIOR | | | FINISHES MUST COMPLY WITH 803,'97SBC. | | | 4]PROVIDE TEST REPORTS FOR WIND AND | | | IMPACT COMPLIANCE ON ALL EXTERIOR DOOR | | | AND WINDOW SYSTEMS. | | | 5]DOORS #24 AND 25 MUST BE APPROVED TYPE | | | DOORS,SEE 1012SBC. | | | 6]DOORS #6,20,25,AND26 MUST BE 20 MIN. | | | RATED IF PART OF THE EXIT ACCESS. | | | 7]DOORS 15 AND 16 MUST COMPLY WITH '97 | | | FAC,4.13.6[MANUVERING CLEARENCES FROM | | | PULL SIDE]. | | | 8]ENTRY CANOPY'S SHALL COMPLY WITH APPEN | | | "F",102.2.8 | | | 9]TYPE 2 CONSTRUCTION REQUIRES ANY WOOD | | | USED,SHALL BE OF FIRE RETARDANT TREAT- | | | ED. | | | 10]SPECIFY WHICH CODE WAS USED FOR THE | | | DESIGN CALCULATION,EACH PAGE SHALL BE | | | SIGNED AND SEALED. | | | 11]SUBMIT ENERGY EFFICIENCY CALCULATIONS | | | 12]PROVIDE ACCESSIBLE SEATING FOR DINING | | | PATIO"C". | | | 13]SUBMIT FIRE SPRINKLER LAYOUT. | | | | | | REVIEWED BY | | | LUIS MARTINEZ | | | 561-659-8096#8456 |
|