| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-IMPACT FEES WERE NOT PAID. |
| | 2-EXTERIOR ELEVATIONS DON'T MATCH FLOOR |
| | PLAN. REVISE AS REQUIRED. |
| | 3-PROVIDE SAFETY GLASS AT BEDROOM #2 |
| | WINDOW. SECTION 2405.2 SBC 1997. |
| | 4-ENGINEER OF RECORD TO SIGN, SEAL AND |
| | DATE SHEET A-3. ALSO, INCLUDE HIS |
| | NAME, LICENSE # AND ADDRESS. |
| | 5-REVISE SIZES OF CEILING FANS. SEE |
| | TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY |
| | CODE FOR BUILDING CONSTRUCTION,1997 ED |
| | 6-PROVIDE COPIES OF SOIL TEST REPORT |
| | DONE AS PER SECTION 1804.2.7.3 OF CITY |
| | AMENDMENTS. |
| | 7-PROVIDE COMPLETE DETAIL FOR AHU |
| | INSTALLATION. SPECIFY ALL FASTENERS. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | BUTT GLAZING ASSEMBLY AT MASTER BATH, |
| | ALL FRENCH DOORS ASSEMBLIES AS SHOWN |
| | ON PLANS, DOUBLE ENTRY INSWING DOORS, |
| | FIXED GLASS TRANSOM ABOVE DOORS IN |
| | LIVING ROOM -SEE SIZE, WINDOW MULLIONS |
| | 9-BEFORE SUBMITTING PRODUCT APPROVAL FOR |
| | FRENCH DOORS AND ENTRY DOORS CHECK IF |
| | INSTALLATION REQUIRES A 2X BUCK. IF SO |
| | PROVIDE INSTALLATION DETAIL. |
| | 10-SEE COMMENTS ON PLANS, INCLUDING |
| | COMMENTS BY THE OTHER TRADES. |
| | 11-OWES $FOR LOW VALUATION AND |
| | RADON FEES. SEE ATTACHED RECEIPT. |