Plan Review Notes
Plan Review Notes For Permit 00050050
Permit Number 00050050
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE INCLUDE BLDG. STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 AS PER 250-50
  
 2)NOTE: PLEASE NOTE THAT ALL THE OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE LABEL AS GFI.
 AS PER 210-8-A-6
  
 3)NOTE: YOU HAVE A NOTE ON RISER DIAGRAM
 THAT MAIN DISC. WITH CURRENT LIMITING
 FUSES? BUT THERE IS NO DISC. YOU SHOW
 MAIN BRKR PANEL? PLEASE PROVIDE AIC RAT-
 -ING FOR MAIN ON PANEL OR WHATEVER
 EQUIPMENT IS BEING INSTALLED? SHOW THE
 RATING. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT.110-9
 PLEASE SHOW THE ABOVE PER 215-5
  
  
 4)NOTE:PLEASE SHOW ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-11-C-3/215-5
  
 5)NOTE:PLEASE NOTE THE MISSING OUTLETS
 THAT ARE REQ`D BY 210-52
 IN FRONT FOYER ARE AND ADJOINING ROOM
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372