| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE INCLUDE BLDG. STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | AS PER 250-50 | | | | | | 2)NOTE: PLEASE NOTE THAT ALL THE OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. PLEASE LABEL AS GFI. | | | AS PER 210-8-A-6 | | | | | | 3)NOTE: YOU HAVE A NOTE ON RISER DIAGRAM | | | THAT MAIN DISC. WITH CURRENT LIMITING | | | FUSES? BUT THERE IS NO DISC. YOU SHOW | | | MAIN BRKR PANEL? PLEASE PROVIDE AIC RAT- | | | -ING FOR MAIN ON PANEL OR WHATEVER | | | EQUIPMENT IS BEING INSTALLED? SHOW THE | | | RATING. MAINS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.110-9 | | | PLEASE SHOW THE ABOVE PER 215-5 | | | | | | | | | 4)NOTE:PLEASE SHOW ON PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | | PER 210-11-C-3/215-5 | | | | | | 5)NOTE:PLEASE NOTE THE MISSING OUTLETS | | | THAT ARE REQ`D BY 210-52 | | | IN FRONT FOYER ARE AND ADJOINING ROOM | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. 659-8096 EXT 8372 |
|