| Plan Review Notes For Permit 00050040 |
| Permit Number |
00050040 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE SAFETY GLASS AT BEDROOM #2. | | | SECTION 2405.2 SBC 1997. | | | 2-PROVIDE PRODUCT APPROVAL FOR BUTT | | | GLAZING ASSEMBLY AT MASTER BATH. | | | 3-PRODUCT APPROVAL FOR SLIDING GLASS | | | DOORS IS NOT GOOD. SEE SIZES SHOWN | | | ON PLANS AND PRODUCT APPROVAL. | | | 4-PROVIDE COMPLETE INSTALLATION DETAIL/ | | | SPECS FOR AHU IN ATTIC. INCLUDE ALL | | | HANGERS. SEC 104.2.2 CITY AMENDMENTS. | | | 5-PROVIDE COPIES OF SOIL TEST REPORT | | | DONE AS PER SEC 1804.2.7.3 OF CITY | | | AMENDMENTS. | | | 6-PROVIDE PRODUCT APPROVAL FOR INSWING | | | DOUBLE ENTRY DOORS. | | | 7-PROVIDE STRUCTURAL BUCK DETAIL WITH A | | | 2X BUCK IF REQUIRED IN THE DOORS | | | PRODUCT APPROVAL. | | | 8-PROVIDE PRODUCT APPROVAL FOR: | | | -WINDOW MULLIONS, FRENCH DOOR AT MASTER | | | SUITE, FIXED WINDOW OF THE SIZE SHOWN | | | AT THE LIVING ROOM ABOVE THE SLIDING | | | GLASS DOORS. | | | 9-REVISE SIZE OF CEILING FANS. SEE TABLE | | | 6-6 OF FLORIDA ENERGY EFFICIENCY CODE | | | FOR BUILDING CONSTRUCTION. 1997 ED. | | | 10-SEE COMMNETS ON PLANS, INCLUDING THE | | | OTHER TRADES. |
|