| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-IMPACT FEES WERE NOT PAID. |
| | 2-PROVIDE SAFETY GLAZING AT BEDROOM #2. |
| | SECTION 2405.2 SBC 1997. |
| | 3-PROVIDE PRODUCT APPROVAL FOR BUTT |
| | GLAZING ASSEMBLY AT MASTER BATH. |
| | 4-PRODUCT APPROVAL FOR SLIDING GLASS |
| | DOORS IS NO GOOD. SIZE OF DOORS SHOWN |
| | ON LIVING ROOM IS NOT COVERED IN THIS |
| | PRODUCT APPROVAL. RESUBMIT. |
| | 5-PROVIDE COMPLETE INSTALLATION DETAIL/ |
| | SPECIFICATIONS FOR AHU IN ATTIC. |
| | INCLUDE ALL FASTENERS. |
| | 6-PROVIDE COPIES OF SOIL TEST REPORT |
| | DONE AS PER SEC 1804.2.7.3 OF CITY |
| | AMENDMENTS. |
| | 7-INSWING PRODUCT APPROVAL SUBMITTED IS |
| | FOR SINGLE DOOR ONLY. PROVIDE PRODUCT |
| | APPROVAL FOR INSWING DOUBLE DOORS. |
| | 8-PROVIDE STRUCTURAL BUCK DETAIL WITH |
| | 2X BUCK IF REQUIRED IN THE PRODUCT |
| | APPROVAL REQUIREMENTS. |
| | 9-PROVIDE PRODUCT APPROVAL FOR: |
| | WINDOW MULLIONS, FRENCH DOOR AT MASTER |
| | SUITE, FIXED WINDOW OF THE SIZE SHOWN |
| | AT THE LIVING ROOM ABOVE THE SLIDING |
| | GLASS DOORS. |
| | 10-REVISE SIZE OF CEILING FANS. SEE |
| | TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY |
| | CODE FOR BUILDING CONSTRUCTION. |
| | 11-SEE COMMENTS ON PLANS, INCLUDING THE |
| | COMMENTS BY THE OTHER TRADES. |