2001-01-08 00:00:00CHECKLIST:
 1-IMPACT FEES WERE NOT PAID.
 2-PROVIDE SAFETY GLAZING AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING ASSEMBLY AT MASTER BATH.
 4-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS IS NO GOOD. SIZE OF DOORS SHOWN
 ON LIVING ROOM IS NOT COVERED IN THIS
 PRODUCT APPROVAL. RESUBMIT.
 5-PROVIDE COMPLETE INSTALLATION DETAIL/
 SPECIFICATIONS FOR AHU IN ATTIC.
 INCLUDE ALL FASTENERS.
 6-PROVIDE COPIES OF SOIL TEST REPORT
 DONE AS PER SEC 1804.2.7.3 OF CITY
 AMENDMENTS.
 7-INSWING PRODUCT APPROVAL SUBMITTED IS
 FOR SINGLE DOOR ONLY. PROVIDE PRODUCT
 APPROVAL FOR INSWING DOUBLE DOORS.
 8-PROVIDE STRUCTURAL BUCK DETAIL WITH
 2X BUCK IF REQUIRED IN THE PRODUCT
 APPROVAL REQUIREMENTS.
 9-PROVIDE PRODUCT APPROVAL FOR:
 WINDOW MULLIONS, FRENCH DOOR AT MASTER
 SUITE, FIXED WINDOW OF THE SIZE SHOWN
 AT THE LIVING ROOM ABOVE THE SLIDING
 GLASS DOORS.
 10-REVISE SIZE OF CEILING FANS. SEE
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION.
 11-SEE COMMENTS ON PLANS, INCLUDING THE
 COMMENTS BY THE OTHER TRADES.