| Plan Review Notes For Permit 00050040 |
| Permit Number |
00050040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE:PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS REQ`D BY 210-8-A-6 | | | | | | 2)NOTE:BLDG.STEEL TO BE PART OF THE | | | GROUNDING ELECTRODE SYSTEM AS PER 250-50 | | | SHOW ON PLANS . | | | | | | 3)NOTE:RISER DIAGRAM NOTE NOTES FUSED | | | DISC? NOT SHOWN? PLEASE SUBMIT CORRECT | | | RISER DIAGRAM. MAIN MUST BE RATED FOR TH | | | AVIALABLE FAULT CURRENT. 110-9 | | | | | | 4)NOTE: PLEASE NOTE THE MISSING OUTLETS | | | REQ`D BY 210-52 FRONT FOYER ARE AND AD- | | | -JOINING AREA. | | | 5)NOTE: PLEASE SHOW ON PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | | PER 210-11-C-3 MUST BE 20A AND #12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REIVEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|