Plan Review Notes
Plan Review Notes For Permit 00050040
Permit Number 00050040
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS REQ`D BY 210-8-A-6
  
 2)NOTE:BLDG.STEEL TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM AS PER 250-50
 SHOW ON PLANS .
  
 3)NOTE:RISER DIAGRAM NOTE NOTES FUSED
 DISC? NOT SHOWN? PLEASE SUBMIT CORRECT
 RISER DIAGRAM. MAIN MUST BE RATED FOR TH
 AVIALABLE FAULT CURRENT. 110-9
  
 4)NOTE: PLEASE NOTE THE MISSING OUTLETS
 REQ`D BY 210-52 FRONT FOYER ARE AND AD-
 -JOINING AREA.
 5)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-11-C-3 MUST BE 20A AND #12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372