2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE SAFETY GLASS AT BEDROOM #2
 WINDOW. SECTION 2405.2 SBC 1997.
 2-REVISE SIZE OF CEILING FANS. SEE TABLE
 6-6 OF FLORIDA ENERGY EFFICIENCY CODE
 FOR BUILDING CONSTRUCTION. 1997 ED.
 3-PROVIDE COPIES OF SOIL TEST REPORTS
 DONE AS PER SECTION 1804.2.7.3 OF
 CITY AMENDMENTS.
 4-PROVIDE COMPLETE DETAIL FOR AHU
 INSTALLATION. SPECIFY ALL HANGERS.
 SECTION 104.2.2 CITY AMENDMENTS
 5-PROVIDE PRODUCT APPROVAL FOR:
 -BUTT GLAZING ASSEMBLY AT MASTER BATH,
 FRENCH DOOR AT MASTER SUITE, SLIDING
 GLASS DOORS (SEE SIZES SHOWN ON THE
 ARCHITCTURAL PLANS), DOUBLE INSWING
 ENTRY DOORS, FIXED GLASS ABOVE DOORS
 IN LIVING ROOM (SEE SIZE) AND WINDOW
 MULLIONS.
 6-IF PRODUCT APPROVAL FOR SWING DOORS
 REQUIRES TO USE A 2X BUCK, THEN
 PROVIDE SUCH DETAIL.
 7-SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.