| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE SAFETY GLASS AT BEDROOM #2 | | | WINDOW. SECTION 2405.2 SBC 1997. | | | 2-REVISE SIZE OF CEILING FANS. SEE TABLE | | | 6-6 OF FLORIDA ENERGY EFFICIENCY CODE | | | FOR BUILDING CONSTRUCTION. 1997 ED. | | | 3-PROVIDE COPIES OF SOIL TEST REPORTS | | | DONE AS PER SECTION 1804.2.7.3 OF | | | CITY AMENDMENTS. | | | 4-PROVIDE COMPLETE DETAIL FOR AHU | | | INSTALLATION. SPECIFY ALL HANGERS. | | | SECTION 104.2.2 CITY AMENDMENTS | | | 5-PROVIDE PRODUCT APPROVAL FOR: | | | -BUTT GLAZING ASSEMBLY AT MASTER BATH, | | | FRENCH DOOR AT MASTER SUITE, SLIDING | | | GLASS DOORS (SEE SIZES SHOWN ON THE | | | ARCHITCTURAL PLANS), DOUBLE INSWING | | | ENTRY DOORS, FIXED GLASS ABOVE DOORS | | | IN LIVING ROOM (SEE SIZE) AND WINDOW | | | MULLIONS. | | | 6-IF PRODUCT APPROVAL FOR SWING DOORS | | | REQUIRES TO USE A 2X BUCK, THEN | | | PROVIDE SUCH DETAIL. | | | 7-SEE COMMENTS ON PLANS. INCLUDING THOSE | | | BY THE OTHER TRADES. |
|