| Plan Review Notes For Permit 00050037 |
| Permit Number |
00050037 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-IMPACT FEES WERE NOT PAID. | | | 2-PROVIDE SAFETY GLASS AT BEDROOM #2 | | | WINDOW. SECTION 2405.2 SBC 1997. | | | 3-REVISE SIZES OF CEILING FANS. SEE | | | TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY | | | CODE FOR BUILDING CONSTRUCTION. | | | 4-PROVIDE COPIES OF SOIL TEST REPORT | | | DONE AS PER SECTION 1804.2.7.3 OF | | | CITY AMENDMENTS. | | | 5-PROVIDE COMPLETE DETAIL FOR AHU | | | INSTALLATION. SPECIFY ALL FASTENERS. | | | SECTION 104.2.2 CITY AMENDMENTS. | | | 6-PROVIDE PRODUCT APPROVAL FOR: | | | BUTT GLAZING ASSEMBLY AT MASTER BATH, | | | FRENCH DOOR AT MASTER SUITE, SLIDING | | | GLASS DOORS (SEE SIZES SHOWN ON THE | | | ARCHITECTURAL PLANS), DOUBLE INSWING | | | DOORS AT ENTRY, FIXED GLASS ABOVE | | | DOORS IN LIVING ROOM (SEE SIZE) AND | | | WINDOW MULLIONS. | | | 7-IF PRODUCT APPROVAL FOR SWING DOORS | | | REQUIRE TO USE A 2X BUCK, THEN PROVIDE | | | SUCH DETAIL. | | | 8-SEE COMMENTS ON PLANS. INCLUDING THE | | | OTHER TRADES. | | | 9-OWES $FOR LOW VALUATION AND | | | RADON FEES. SEE ATTACHED RECEIPT. |
|