Plan Review Notes
Plan Review Notes For Permit 00050035
Permit Number 00050035
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-REVISE ENERGY CALCULATIONS: THERE ARE
 FOUR BEDROOMS, NOT 3. SEE PLANS.
 2-PROFESSIONAL ENGINEER SHOULD NOT SEAL
 ORIGINAL DRAWINGS. SEC 61G15-23.002.
 ALSO, SURVEYOR TO PROVIDE WET
 SIGNATURE AND DATE WHEN SEALING DWG.
 3-PROVIDE PRODUCT APPROVAL FOR:
 -ONE HOUR FIRE RATED EGRESS PANEL.
 -DOUBLE ENTRY DOORS.
 -FRENCH DOORS.
 -GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 -WINDOW MULLIONS.
 -FIXED WINDOWS WITH THE SIZES SHOWN AT
 THE GREAT ROOM.
 4-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCH. INCLUDE FASTENER TYPE AND
 SPACING. SECTION 2504 SBC 1997.
 5-SPECIFY SIZE OF ATTIC ACCESS PANELS.
 SECTION 2309.6 SBC 1997.
 6-PROVIDE COMPLETE CONNECTION DETAIL AT
 BOTTOM OF STEEL COLUMNS. SEC 104.2.2
 7-REVISE TYPICAL WALL SECTION AND
 FOUNDATION NOTES. MINIMUM 6 MIL VAPOR
 BARRIER. SECTION 1909.2 SBC 1997.
 8-SPECIFY SIZE OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION, 1997
 9-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM:
 -MEAN ROOF HEIGHT IS WRONG. MEAN ROOF
 HEIGHT IS TAKEN FROM GRADE, NOT FROM
 FINISH FLOOR, TO THE AVERAGE POINT OF
 THE HIGHEST ROOF.
 -SEE CHAPTER 16 OF SBC 1997 FOR THE
 CORRECT VALUES FOR THE BASIC VELOCITY
 PRESSURE AND THE IMPORTANCE FACTOR.
 10-PROVIDE COPIES OF THE SOIL TESTS DONE
 AS PER SEC 1804.2.7.3 CITY AMENDMENTS
 11-ARCHITECT'S GENERAL NOTES ON SHEET GN
 SPECIFIES WINDOWS, DOORS AND ROOF TILE
 WHICH ARE DIFFERENT FROM THE PRODUCT
 APPROVALS SUBMITTED. ARCHITECT TO
 APPROVE ALL PRODUCT APPROVALS PRIOR TO
 SUBMITTAL TO THIS OFFICE.
 12-SEE COMMENTS ON PLANS, INCLUDING
 THOSE BY THE OTHER TRADES AND REVISE
 ORIGINALS AS REQUIRED.
  
  
 NOTE:
  
 INFORMATION REQUESTED ON THIS PROVISO
 SHALL BE SUBMITTED PRIOR TO INSTALLATION
 TO AVOID CONFLICT OR DELAYS.