Plan Review Notes
Plan Review Notes For Permit 00041440
Permit Number 00041440
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT GAS DRAWING FOR ALL GAS WORK.SHOW
 ALL PIPE SIZES,TYPE OF PIPING,DIMENSIONS
 OF ALL CUT SECTIONS OF PIPE,BTU LOAD,ETC
  
 GAS WATER IN GARAGE SHALL BE PROTECTED
 AND INSTALLED MIN.18" ABOVE THE FLOOR
 PER SGC SECS.402.7.1,402.7.2.
  
 SPACING OF WATER CLOSET AND BIDET SHALL
 COMPLY W/SPC SEC.403.4.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 DRY VENTS NOT PERMITTED PER SPC 906.2.1.