| Plan Review Notes For Permit 00041354 |
| Permit Number |
00041354 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT THE AIC RATING | | | OF EQUIPMENT MAINS AND PANELS.215-5 | | | MAINS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT AS PER 110-9 | | | | | | 2)NOTE: NEED TO HAVE THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) TO BE 20 AMP AND #12 | | | AWG. AS PER 210-11-C-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 | | | | | | | | | ***************NOTE********************* | | | | | | SHEET A-4(ELEC) MAY BE CHANGED OUT | | | BY ARCH ENT. BEFORE BLDG.DOES THEIR PLAN | | | REVIEW. THIS WAY MAYBE THE PLANS WON`T | | | HAVE TO COME BACK JUST FOR ELEC. COMMENT | | | -S. |
|