Plan Review Notes
Plan Review Notes For Permit 00041319
Permit Number 00041319
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-18 00:00:00NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 AN EXISTING OR NEW BUILDINGS SHALL NOT
 BE OCCUPIED FOR ANY PURPOSE WHICH WILL
 CAUSE THE FLOORS THEREOF TO BE LOADED
 BEYOND THEIR SAFE CAPACITY. THE BUILDING
 OFFICIAL MAY PERMIT OCCUPANCY OF A BUILD
 ING FOR MERCANTILE, COMMERCIAL, OR IN-
 DUSTRIAL PURPOSES, BY A SPECIFIC BUSSIN-
 ESS WHEN HE/SHE IS SATISFIED THAT SUCH
 CAPACITY WILL NOT THEREBY BE EXCEEDED.