| Plan Review Notes For Permit 00041319 |
| Permit Number |
00041319 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | | | | PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | AN EXISTING OR NEW BUILDINGS SHALL NOT | | | BE OCCUPIED FOR ANY PURPOSE WHICH WILL | | | CAUSE THE FLOORS THEREOF TO BE LOADED | | | BEYOND THEIR SAFE CAPACITY. THE BUILDING | | | OFFICIAL MAY PERMIT OCCUPANCY OF A BUILD | | | ING FOR MERCANTILE, COMMERCIAL, OR IN- | | | DUSTRIAL PURPOSES, BY A SPECIFIC BUSSIN- | | | ESS WHEN HE/SHE IS SATISFIED THAT SUCH | | | CAPACITY WILL NOT THEREBY BE EXCEEDED. |
|