Plan Review Notes
Plan Review Notes For Permit 00041284
Permit Number 00041284
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CONTINUATION OF PLUMBING COMMENTS:
 24)CIRCUIT AND LOOP SYSTEM SHALL COMPLY
 W/SPC SEC.914.1,914.2.
  
 25)A VENT IS REQD.BETWEEN THE SHOWER AND
 THE JANITOR SINK.SPC SEC.901.2.
  
 26)WATER CLOSETS AND FIXTURE DRAINS ARE
 NOT PERMITTED ON WET VENTS PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.911.1.1.
  
 27)TWO WATER CLOSETS SHALL BE VENTED PER
 COUNTYWIDE AMENDMENTS SEC.911.1.3.
  
 28)FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 29)SUBMIT COMPLETE SANITARY AND WATER
 RISERS FOR ALL AREAS.(KIT.,3RD.FLR.,ETC.
  
 30)SANITARY RISER SHALL CORRELATE W/
 FLOOR PLAN.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 31)A PERMIT MAY BE REQD.FROM DEPT.OF
 ENVIRONMENTAL PROTECTION FOR THE WATER
 AND SANITARY LINE.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.