Plan Review Notes
Plan Review Notes For Permit 00041284
Permit Number 00041284
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT COPY OF JOB SPECIFICATIONS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.,104.2.2.
  
 2)ALL DRAWINGS SHALL BE SIGNED/SEALED
 PER COUNTYWIDE AMENDMENTS TO SBC SEC.
 104.2.3,FLA.STATUTE 471 & 481.
  
 3)SUBMIT OCCUPANT LOAD BASED UPON
 HABITABLE FLOOR SPACE AS MANDATED BY SPC
 SEC.407.1.3.MINIMUM SANITARY FACILITIES
 SHALL BE BASED UPON THIS OCCUPANT LOAD.
  
 4)AN ADDITIONAL STALL 36" WIDE W/
 PARALLEL GRAB BARS & OUTSWINGING DOOR
 SHALL BE PROVIDED PER FACBC SEC.4.22.4.
  
 5)NUMBER OF SANITARY FACILITIES SHALL
 COMPLY W/FLA.STATUTE 553.141.(3)."POTTY
 PARITY"
  
 6)DRESSING ROOMS SHALL COMPLY W/FACBC
 SECS.4.1.3(21),4.35.1-4.35.5.(A BENCH IS
 REQD.IN THE ROOM.)
  
 7)ALL PUBLIC USE AND COMMON USE TOILET
 ROOMS SHALL BE ACCESSIBLE PER FACBC
 SEC.4.1.3(11)
  
 8)DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQD.REQUIRED FOR ANY
 FIXTURE PER FACBC SEC.4.22.2.(SEE
 URINALS IN ROOMS 107,206.
  
 9)THE PLUMBING CODE IN EFFECT IS THE
 1994 EDITION.PLUMBING DESIGN,FIXTURES,
 ETC.SHALL CONFORM TO THIS STANDARD.
  
 10)SUBMIT COMPLETE STORM DRAINAGE
 ISOMETRIC.SHOW ALL PIPE SIZES,SQ.FOOT
 AREA DRAINED BY EACH DRAIN,SLOPE OF PIPE
 ETC.COMPLY W/SPC SEC.1108.1,1108.2 FOR
 CORRECT SIZING.
  
 11)MOUNTING HEIGHTS/DIMENSIONS FOR H.C.
 APPURTENANCES SHALL COMPLY W/FACBC 1997
 EDITION.
  
 12)SHOW LOCATION OF H.C.URINALS ON PLANS
 AND SHOW REQD.CLEAR FLOOR SPACE PER
 FACBC SEC.4.18.3.
  
 13)SHT.A-13-URINALS SHALL BE LOCATED TO
 ENSURE PRIVACY.(THEY ARE LOCATED IN THE
 LINE OF SIGHT FROM THE CORRIDOR.)RM.206.
  
 14.)SHT.A-13-ROOM#206-SIZE OF THE
 HANDICAP STALL SHALL COMPLY W/FACBC SEC.
 4.17.3.OF THE FACBC.(SEE EXCEPTION :NEW
 CONSTRUCTION.)
  
 15)SHT.A-13-SHOW THE CLEAR DIMENSIONS OF
 ALL H.C. TOILET STALLS.COMPLY W/FCBC
 SEC.4.17.3.
  
 16)SHOW RED.WHEELCHAIR TURNING SPACE IN
 THE TOILET ROOMS PER FACBC SEC.4.2.3.
  
 17)INDICATE ON PLAN IF A PUMP AND DRAIN
 LINE WILL BE INSTALLED IN THE ELEVATOR
 SUMP.IF SO,SUBMIT PIPING ISOMETRIC FOR
 REVIEW.IF ELEVATOR IS HYDRAULIC AN
 INTERCEPTOR WILL BE REQD.
  
 18)SHT.P01-GREASE TRAP DETAIL SHALL
 COMPLY W/CITY OF WPB STANDARDS.A TWO WAY
 CLEANOUT SHALL BE INSTALLED ENTERING AND
 LEAVING EACH INTERCEPTOR.
  
 19)CAPACITY OF GREASE TRAP SHALL BE
 APPROVED BY CITY OF WEST PALM BEACH
 UTILITIES.CONTACT R.COMPO OR BONNIE KAMP
 AT 835-7423.SUBMIT COPY OF APPROVAL FORM
 FROM UTILITIES.
  
 20)PLANSSHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 21)A VACUUM RELIEF VALVE SHALL BE IN-
 STALLED ON THE COLD WATER SUPPLY TO THE
 WATER HEATER PER SPC.SEC.507.1.2.
  
 22)SUBMIT MANUF.SHEETS FOR ALL GAS
 EQUIPMENT.EQUIPMENT SHALL BE LISTED PER
 SGC SEC.402.1.
  
 23)SHT.P6-URINAL SHALL BE VENTED.SPC
 SEC.901.2.
 SEE STEP #2 FOR CONTINUATION OF PLBG.