| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT COPY OF JOB SPECIFICATIONS FOR |
| | REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1.,104.2.2. |
| | |
| | 2)ALL DRAWINGS SHALL BE SIGNED/SEALED |
| | PER COUNTYWIDE AMENDMENTS TO SBC SEC. |
| | 104.2.3,FLA.STATUTE 471 & 481. |
| | |
| | 3)SUBMIT OCCUPANT LOAD BASED UPON |
| | HABITABLE FLOOR SPACE AS MANDATED BY SPC |
| | SEC.407.1.3.MINIMUM SANITARY FACILITIES |
| | SHALL BE BASED UPON THIS OCCUPANT LOAD. |
| | |
| | 4)AN ADDITIONAL STALL 36" WIDE W/ |
| | PARALLEL GRAB BARS & OUTSWINGING DOOR |
| | SHALL BE PROVIDED PER FACBC SEC.4.22.4. |
| | |
| | 5)NUMBER OF SANITARY FACILITIES SHALL |
| | COMPLY W/FLA.STATUTE 553.141.(3)."POTTY |
| | PARITY" |
| | |
| | 6)DRESSING ROOMS SHALL COMPLY W/FACBC |
| | SECS.4.1.3(21),4.35.1-4.35.5.(A BENCH IS |
| | REQD.IN THE ROOM.) |
| | |
| | 7)ALL PUBLIC USE AND COMMON USE TOILET |
| | ROOMS SHALL BE ACCESSIBLE PER FACBC |
| | SEC.4.1.3(11) |
| | |
| | 8)DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQD.REQUIRED FOR ANY |
| | FIXTURE PER FACBC SEC.4.22.2.(SEE |
| | URINALS IN ROOMS 107,206. |
| | |
| | 9)THE PLUMBING CODE IN EFFECT IS THE |
| | 1994 EDITION.PLUMBING DESIGN,FIXTURES, |
| | ETC.SHALL CONFORM TO THIS STANDARD. |
| | |
| | 10)SUBMIT COMPLETE STORM DRAINAGE |
| | ISOMETRIC.SHOW ALL PIPE SIZES,SQ.FOOT |
| | AREA DRAINED BY EACH DRAIN,SLOPE OF PIPE |
| | ETC.COMPLY W/SPC SEC.1108.1,1108.2 FOR |
| | CORRECT SIZING. |
| | |
| | 11)MOUNTING HEIGHTS/DIMENSIONS FOR H.C. |
| | APPURTENANCES SHALL COMPLY W/FACBC 1997 |
| | EDITION. |
| | |
| | 12)SHOW LOCATION OF H.C.URINALS ON PLANS |
| | AND SHOW REQD.CLEAR FLOOR SPACE PER |
| | FACBC SEC.4.18.3. |
| | |
| | 13)SHT.A-13-URINALS SHALL BE LOCATED TO |
| | ENSURE PRIVACY.(THEY ARE LOCATED IN THE |
| | LINE OF SIGHT FROM THE CORRIDOR.)RM.206. |
| | |
| | 14.)SHT.A-13-ROOM#206-SIZE OF THE |
| | HANDICAP STALL SHALL COMPLY W/FACBC SEC. |
| | 4.17.3.OF THE FACBC.(SEE EXCEPTION :NEW |
| | CONSTRUCTION.) |
| | |
| | 15)SHT.A-13-SHOW THE CLEAR DIMENSIONS OF |
| | ALL H.C. TOILET STALLS.COMPLY W/FCBC |
| | SEC.4.17.3. |
| | |
| | 16)SHOW RED.WHEELCHAIR TURNING SPACE IN |
| | THE TOILET ROOMS PER FACBC SEC.4.2.3. |
| | |
| | 17)INDICATE ON PLAN IF A PUMP AND DRAIN |
| | LINE WILL BE INSTALLED IN THE ELEVATOR |
| | SUMP.IF SO,SUBMIT PIPING ISOMETRIC FOR |
| | REVIEW.IF ELEVATOR IS HYDRAULIC AN |
| | INTERCEPTOR WILL BE REQD. |
| | |
| | 18)SHT.P01-GREASE TRAP DETAIL SHALL |
| | COMPLY W/CITY OF WPB STANDARDS.A TWO WAY |
| | CLEANOUT SHALL BE INSTALLED ENTERING AND |
| | LEAVING EACH INTERCEPTOR. |
| | |
| | 19)CAPACITY OF GREASE TRAP SHALL BE |
| | APPROVED BY CITY OF WEST PALM BEACH |
| | UTILITIES.CONTACT R.COMPO OR BONNIE KAMP |
| | AT 835-7423.SUBMIT COPY OF APPROVAL FORM |
| | FROM UTILITIES. |
| | |
| | 20)PLANSSHALL BE ROUTED TO DEPT.OF |
| | BUSINESS REGULATION FOR REVIEW.COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| | |
| | 21)A VACUUM RELIEF VALVE SHALL BE IN- |
| | STALLED ON THE COLD WATER SUPPLY TO THE |
| | WATER HEATER PER SPC.SEC.507.1.2. |
| | |
| | 22)SUBMIT MANUF.SHEETS FOR ALL GAS |
| | EQUIPMENT.EQUIPMENT SHALL BE LISTED PER |
| | SGC SEC.402.1. |
| | |
| | 23)SHT.P6-URINAL SHALL BE VENTED.SPC |
| | SEC.901.2. |
| | SEE STEP #2 FOR CONTINUATION OF PLBG. |