| Plan Review Notes For Permit 00041284 |
| Permit Number |
00041284 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************DENIED***************** | | | INSUFFICIENT INFORMATION PROVIDED FOR | | | REVIEW. | | | OUTSIDE-AIR NEEDS TO BE ASHRAE 62-89 EG: | | | LOCKER ROOM=60 CFM/PERSON. | | | PROVIDE AIRBALANCE SCHEDULE PER 1997 SMC | | | 501.2 | | | PROVIDE GRILLE SIZES CFM VALUE, DUCT | | | SIZES FOR RETURN AIR & SUPPLY AIR. |
|