Plan Review Notes
Plan Review Notes For Permit 00041284
Permit Number 00041284
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*****************DENIED*****************
 INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW.
 OUTSIDE-AIR NEEDS TO BE ASHRAE 62-89 EG:
 LOCKER ROOM=60 CFM/PERSON.
 PROVIDE AIRBALANCE SCHEDULE PER 1997 SMC
 501.2
 PROVIDE GRILLE SIZES CFM VALUE, DUCT
 SIZES FOR RETURN AIR & SUPPLY AIR.