| Plan Review Notes For Permit 00041284 |
| Permit Number |
00041284 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | FIRE HYDRANT SHALL BE LOCATED W/I 150 FT | | | OF FIRE DEPARTMENT CONNECTION. | | | EMERGENCY LIGHTS SHALL BE SO LOCATED AS | | | TO PROVIDE THE REQUIRED ILLUMINATION IN | | | THE EVENT OF ANY INTERRUPTION OF NORMAL | | | LIGHTING. | | | PROVIDE PANIC HARDWARE ON ALL DESIGNATED | | | EXIT DOORS. | | | ANY USABLE SPACE UNDER STAGE SHALL BE | | | PROTECTED BY FIRE SPRINKLERS. | | | STAGE REQUIREMENTS SHALL COMPLY WITH | | | SECTION 8-3, OF THE 1985 LIFE SAFETY | | | CODE. | | | FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE. | | | INTERIOR FINISH SHALL BE CLASS A OR B. | | | KITCHEN HOOD EXTINGUISHING SYSTEM SHALL | | | BE CONNECTED TO FIRE ALARM SYSTEM. |
|