Plan Review Notes
Plan Review Notes For Permit 00041284
Permit Number 00041284
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00FIRE HYDRANT SHALL BE LOCATED W/I 150 FT
 OF FIRE DEPARTMENT CONNECTION.
 EMERGENCY LIGHTS SHALL BE SO LOCATED AS
 TO PROVIDE THE REQUIRED ILLUMINATION IN
 THE EVENT OF ANY INTERRUPTION OF NORMAL
 LIGHTING.
 PROVIDE PANIC HARDWARE ON ALL DESIGNATED
 EXIT DOORS.
 ANY USABLE SPACE UNDER STAGE SHALL BE
 PROTECTED BY FIRE SPRINKLERS.
 STAGE REQUIREMENTS SHALL COMPLY WITH
 SECTION 8-3, OF THE 1985 LIFE SAFETY
 CODE.
 FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE.
 INTERIOR FINISH SHALL BE CLASS A OR B.
 KITCHEN HOOD EXTINGUISHING SYSTEM SHALL
 BE CONNECTED TO FIRE ALARM SYSTEM.