Plan Review Notes
Plan Review Notes For Permit 00041284
Permit Number 00041284
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PASSED WITH PROVISOS
  
 METER MUST BE LOCATED JUST OUTSIDE OF
 R.O.W. LINE AND BACKFLOW JUST INSIDE
 OF PROPERTY LINE.
  
 EACH SERVICE MUST BE TAPPED SEPERATELY.
  
 NO SADDLE TAPS ALLOWED, ONLY DIRECT TAPS
  
 IF THE PAVEMENT REMOVAL AREA SHOWN IS
 FOR WATER SERVICE THEN IT IS IN THE
 WRONG LOCATION.
  
 PLACE NOTE REFERING TO OUR STANDARD
 PAVEMENT REPLACEMENT DETAIL.
  
 SHOP DRAWINGS MUST BE PROVIDED TO
 MANNY GONZALEZ, PROJECT SPECIALIST
 AT CITY OF WEST PALM BEACH
 PUBLIC UTILITIES ENGINEERING
 1000 45TH ST
 WEST PALM BEACH, FL 33407
 561-659-8040 EXT. 2306