Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:0023)WASTE STACKS CANNOT BE USED FOR VERT-
 ICAL COMBINATION WASTE AND VENT.911.4.
  
 24)HORIZONTAL BRANCH CONNECTIONS CANNOT
 CONNECT TO STACK WITHIN 2 FT.ABOVE OR
 BELOW THE OFFSET.
  
 25)THE FOLLOWING UNITS SHOW THE WATER
 CLOSET IN THE BATHROOM INFRINGING INTO
 REQUIRED CLEAR FLOOR SPACE WHICH IS IN
 VIOLATION OF THE FHA.
 SHT.A433-UNITS B2 & B2A
 SHT.A443-UNIT C6
 SHT.A445-UNIT D2
 SHT.A447-UNIT D4
 SHT.A449-UNIT D5B
 SHT.A450-UNIT D6
 SHT.A451-UNITS D7 & D7A
 SHT.A452-UNIT D8
 SHT.A453-UNIT D9
 THE FOLLOWING UNITS SHOW VIOLATIONS OF
 THE FHA IN THE KITCHEN AREA.
 SHT.A451-UNIT D7A-THE REFRIGERATOR
 INFRINGES ON THE 5'-0"TURNING SPACE.
 COMPLY W/FHA REQ.#7(1)(A)(B)(C).
 SHT.A456-UNIT D13-KITCHEN IS NOT WIDE
 ENOUGH TO COMPLY W/FHA REQ.#7(1)(C).
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.