Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001)SHT.C-6 AND P401-GREASE INTERCEPTORS
 SHALL COMPLY W/CITY OF WPB BLDG.DEPT.
 REQS.SEE ATTACHED.SPC 1004.2
  
 2)SHT.A110-THE NUMBER OF OCCUPANTS FOR
 THE POOL CLUB HOUSE SHALL BE BASED ON
 SQUARE FEET OF HABITABLE FLOOR SPACE
 PER SPC TABLE 407.SEE SPC SEC.407.1.3
 FOR ALLOWED DEDUCTIBLE FLOOR SPACE.
 SHOW OCCUPANT LOAD ON PLANS. A MIN.OF 2
 TOILET ROOMS SHALL BE REQD.
  
 3)SHT.A601-BACKING FOR GRAB BARS FOR TUB
 AT BACK WALLSHALL COMPLY W/FHA REQ.#6,
 FIG.#4.(SEE ATTACHED.)
  
 4)SHT.A601-HEIGHT OF HANDICAP URINAL
 SHALL COMPLY W/FACBC SEC.4.18.2.(MAX.OF
 17"TO TOP OF RIM.)
  
 5)SUBMIT HABITABLE SQUARE FOOT AREA OF
 EACH PUBLIC AND COMMON USE AREA TO
 DETERMINE OCCUPANT LOAD FOR MINIMUM
 SANITARY FACILITY REQS..COMPLY W/SPC
 TABLE 407.RE:EXERCISE AREA,RETAIL,ETC.
  
 6)CLEAR FLOOR SPACE FOR THE SINKS IN THE
 KITCHENS OF THE DWELLING UNITS SHALL BE
 CENTERED ON THE FIXTURE PER FHA 24 CFR
 100.205 REQ.#7(USABLE KITCHENS)AND FAIR
 HOUSING ACT.REFER TO SHEETS A453 UNIT D9
 SHT.A457,UNITS E1 & E1A,SHT.A460,UNIT
 D4A.
  
 7)SHT.A801-DETAIL SHOWS 4" DIA.SCUPPER.
 SUBMIT CALCULATIONS FOR OVERFLOW
 DRAINAGE.COMPLY W/SPC SEC.1109.3 &
 APPENDIX"A".
  
 8)SUBMIT DETAIL OF OIL INTERCEPTOR.SPC
 1004.4.
  
 9)VERTICAL COMBINATION WASTE AND VENTS
 FOR THE KITCHEN SINK SHALL REMAIN
 VERTICAL FROM WASTE STACK OR BRANCH
 BEGINNING AT THE BLDG.DRAIN.SPC SEC.
 911.4.SEE SHTS.P303-308.
  
 10)SOIL AND WASTE STACKS SHALL REMAIN
 UNDIMINISHED IN SIZE FROM THE BUILDING
 DRAIN TO IT'S CONNECTION W/THE STACK
 VENT PER SPC SEC.714.2.
  
 11)SANITARY RISERS SHALL COMPLY W/SPC
 SEC.715.2.(THIS CODE SECTION APPLIES TO
 ALL RISERS DESIGNED IN THE SAME MANNER.
  
 12)RISERS SHALL COMPLY W/SPC SEC.911.3,
 TABLE 911.3.SEE SHT.P304,RISER# S/14.
  
 13)RISERS SHALL COMPLY W/SPC 714.2.
  
 14)FIXTURES ON STACKS ABOVE THE HIGHEST
 WATER CLOSET OR BATHTUB SHALL COMPLY W/
 SPC SEC.913.2.SEE RISER #6 ET.AL.
  
 15)SOIL AND WASTE STACKS IN BUILDINGS
 HAVING MORE THAN TEN BRANCH INTERVALS
 SHALL BE PROVIDED W/RELIEF VENTS AT EACH
 TENTH INTERVAL PER SPC SEC.916.
  
 16)OFFSET VENTS SHALL BE INSTALLED PER
 SPC SEC.715.4,917.1-917.3.SEE SPC SEC.
 715.5 FOR OMISSION OF VENTS.
  
 17)SHT.P315-SHOW SQ.FOOTAGE FOR DRAINS
 FOR PARKING GARAGE.SUBMIT CALCULATIONS
 FOR SECONDARY DRAINAGE.COMPLY W/SPC SEC.
 1109.2,1109.3.& APPENDIX "A".
  
 18)A PERMIT MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION FOR THE WATER
 MAIN INSTALLATION.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 19)SHT.P101-ITEM#12-CLARIFY IF LINE IS
 3"OR 4".SEE SHT.P301.
  
 20)SHT.P301-5TH.FLR.RISER-CIRCUIT AND
 LOOP SHALL COMPLY W/SPC SEC.914.
  
 21)RISER DIAGRAMS SHOW STACKS W/2 HORIZ.
 BRANCHES AT BASE AND SHT.P301 SHOWS 1
 CONNECTION.CLARIFY.
  
 22)MAX.VERTICAL DISTANCE OF COMBINATION
 WASTE AND VENT SHALL COMPLY W/TABLE
 911.4.
  
 SEE PLBG.REVIEW STEP #4 FOR CONTINUATION