| 2001-01-08 00:00:00 | 1)SHT.C-6 AND P401-GREASE INTERCEPTORS |
| | SHALL COMPLY W/CITY OF WPB BLDG.DEPT. |
| | REQS.SEE ATTACHED.SPC 1004.2 |
| | |
| | 2)SHT.A110-THE NUMBER OF OCCUPANTS FOR |
| | THE POOL CLUB HOUSE SHALL BE BASED ON |
| | SQUARE FEET OF HABITABLE FLOOR SPACE |
| | PER SPC TABLE 407.SEE SPC SEC.407.1.3 |
| | FOR ALLOWED DEDUCTIBLE FLOOR SPACE. |
| | SHOW OCCUPANT LOAD ON PLANS. A MIN.OF 2 |
| | TOILET ROOMS SHALL BE REQD. |
| | |
| | 3)SHT.A601-BACKING FOR GRAB BARS FOR TUB |
| | AT BACK WALLSHALL COMPLY W/FHA REQ.#6, |
| | FIG.#4.(SEE ATTACHED.) |
| | |
| | 4)SHT.A601-HEIGHT OF HANDICAP URINAL |
| | SHALL COMPLY W/FACBC SEC.4.18.2.(MAX.OF |
| | 17"TO TOP OF RIM.) |
| | |
| | 5)SUBMIT HABITABLE SQUARE FOOT AREA OF |
| | EACH PUBLIC AND COMMON USE AREA TO |
| | DETERMINE OCCUPANT LOAD FOR MINIMUM |
| | SANITARY FACILITY REQS..COMPLY W/SPC |
| | TABLE 407.RE:EXERCISE AREA,RETAIL,ETC. |
| | |
| | 6)CLEAR FLOOR SPACE FOR THE SINKS IN THE |
| | KITCHENS OF THE DWELLING UNITS SHALL BE |
| | CENTERED ON THE FIXTURE PER FHA 24 CFR |
| | 100.205 REQ.#7(USABLE KITCHENS)AND FAIR |
| | HOUSING ACT.REFER TO SHEETS A453 UNIT D9 |
| | SHT.A457,UNITS E1 & E1A,SHT.A460,UNIT |
| | D4A. |
| | |
| | 7)SHT.A801-DETAIL SHOWS 4" DIA.SCUPPER. |
| | SUBMIT CALCULATIONS FOR OVERFLOW |
| | DRAINAGE.COMPLY W/SPC SEC.1109.3 & |
| | APPENDIX"A". |
| | |
| | 8)SUBMIT DETAIL OF OIL INTERCEPTOR.SPC |
| | 1004.4. |
| | |
| | 9)VERTICAL COMBINATION WASTE AND VENTS |
| | FOR THE KITCHEN SINK SHALL REMAIN |
| | VERTICAL FROM WASTE STACK OR BRANCH |
| | BEGINNING AT THE BLDG.DRAIN.SPC SEC. |
| | 911.4.SEE SHTS.P303-308. |
| | |
| | 10)SOIL AND WASTE STACKS SHALL REMAIN |
| | UNDIMINISHED IN SIZE FROM THE BUILDING |
| | DRAIN TO IT'S CONNECTION W/THE STACK |
| | VENT PER SPC SEC.714.2. |
| | |
| | 11)SANITARY RISERS SHALL COMPLY W/SPC |
| | SEC.715.2.(THIS CODE SECTION APPLIES TO |
| | ALL RISERS DESIGNED IN THE SAME MANNER. |
| | |
| | 12)RISERS SHALL COMPLY W/SPC SEC.911.3, |
| | TABLE 911.3.SEE SHT.P304,RISER# S/14. |
| | |
| | 13)RISERS SHALL COMPLY W/SPC 714.2. |
| | |
| | 14)FIXTURES ON STACKS ABOVE THE HIGHEST |
| | WATER CLOSET OR BATHTUB SHALL COMPLY W/ |
| | SPC SEC.913.2.SEE RISER #6 ET.AL. |
| | |
| | 15)SOIL AND WASTE STACKS IN BUILDINGS |
| | HAVING MORE THAN TEN BRANCH INTERVALS |
| | SHALL BE PROVIDED W/RELIEF VENTS AT EACH |
| | TENTH INTERVAL PER SPC SEC.916. |
| | |
| | 16)OFFSET VENTS SHALL BE INSTALLED PER |
| | SPC SEC.715.4,917.1-917.3.SEE SPC SEC. |
| | 715.5 FOR OMISSION OF VENTS. |
| | |
| | 17)SHT.P315-SHOW SQ.FOOTAGE FOR DRAINS |
| | FOR PARKING GARAGE.SUBMIT CALCULATIONS |
| | FOR SECONDARY DRAINAGE.COMPLY W/SPC SEC. |
| | 1109.2,1109.3.& APPENDIX "A". |
| | |
| | 18)A PERMIT MAY BE REQD.FROM THE DEPT.OF |
| | ENVIRONMENTAL PROTECTION FOR THE WATER |
| | MAIN INSTALLATION.COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.101.4.7. |
| | |
| | 19)SHT.P101-ITEM#12-CLARIFY IF LINE IS |
| | 3"OR 4".SEE SHT.P301. |
| | |
| | 20)SHT.P301-5TH.FLR.RISER-CIRCUIT AND |
| | LOOP SHALL COMPLY W/SPC SEC.914. |
| | |
| | 21)RISER DIAGRAMS SHOW STACKS W/2 HORIZ. |
| | BRANCHES AT BASE AND SHT.P301 SHOWS 1 |
| | CONNECTION.CLARIFY. |
| | |
| | 22)MAX.VERTICAL DISTANCE OF COMBINATION |
| | WASTE AND VENT SHALL COMPLY W/TABLE |
| | 911.4. |
| | |
| | SEE PLBG.REVIEW STEP #4 FOR CONTINUATION |