Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**********PLBG.STEP#2-CONTINUATION OF
 PLUMBING COMMENTS FOR #00041269.
  
 23)SHT.P305-RISER S/3-SHALL COMPLY W/SPC
 SEC.911.3 & TABLE 911.3.(THIS CODE SEC.
 APPLIES TO ALL RISERS DESIGNED IN THE
 SAME MANNER.)
  
 24)SHT,P305-RISERSS/5 & S/20-SHALL
 COMPLY W/SPC SEC.714.2.(APPLIES TO ALL
 RISERS OF THIS DESIGN.)
  
 25)FIXTURES LOCATED ON STACKS ABOVE THE
 HIGHEST WATER CLOSET OR BATHTUB SHALL
 COMPLY W/SPC SEC.913.2.(SEE SHT.P306-
 RISER #S/6 AND ALL OTHERS OF THE SAME
 DESIGN.)
  
 26)RELIEF VENTS ARE REQD.IN SOIL OR
 WASTE STACKS MORE THAN 10 BRANCH INTER-
 VALS PER SPC SEC.916
  
 27)OFFSET VENTS SHALL BE INSTALLED PER
 SPC 917.1,917.2,917.3.(SEE SHT.P306,
 RISERS S/11,S/25, AND ALL OTHER STACKS
 OF THE SAME DESIGN.)
  
 28)SHT.P310-SHOW PIPE SIZES FOR THE
 GREASE WASTE AND SANITARY COLLECTION
 SYSTEMS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 29)SHT.P401-MIN.1"INSULATION IS REQD.ON
 C.W.PIPE AT WATER HEATER PER F.E.C.
 TABLE 4-11.(SEE NOTE #15.)
  
 30)SUBMIT COMPLETE STORM DRAINAGE RISER
 FOR REVIEW.SHOW SQ.FT.AREA DRAINED BY
 EACH DRAIN,PIPE SIZES,SLOPE OF PIPE.
 INCLUDE ALL AREA DRAINS AND DECK DRAINS
 IN THE DRAWING.COUNTYWIDE AMENDMENTS TO
 SPC 104.2.1.
  
 31)SUBMIT PROVISIONS,CALCULATIONS,AND
 DRAWINGS FOR SECONDARY DRAINAGE FOR THE
 ROOF.COMPLY W/SPC SECS.1109.1,1109.2,
 1109.3 AND APPENDIX "A".
  
 32)LAYOUT OF GREASY WASTE SYSTEM ON P310
 DOESN'T CORRELATE W/P102.CLARIFY.
  
 33)SHT.P310 NOTES 8"TO SANITARY AND
 P102 NOTES 6".CLARIFY.(SEE GREASE WASTE)
  
 34)A PERMIT MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION FOR THE WATER
 MAIN INSTALLATION.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 35)REQUIRED NUMBER OF SANITARY FIXTURES
 FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF
 HEALTH CHAPTER 64E-9.APPROVAL REQD.FROM
 HEALTH DEPT.
  
 36)A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE FOUNTAIN.
  
 37)SHT.P312-NOTES ALL P&T LINES AND DP
 LINES AS 1 1/2" AND P101 CALLS OUT
 1 1/4".SHT.P101 ALSO NOTES 1 1/2" LINES
 DISCHARGING INTO A 1 1/4" LINE U/G AND
 A/G.CLARIFY.LINES SHALL NOT BE REDUCED
 IN SIZE PER VALVE MANUF.RECOMMENDATIONS.