| Date |
Text |
| 2001-01-08 00:00:00 | **********PLBG.STEP#2-CONTINUATION OF |
| | PLUMBING COMMENTS FOR #00041269. |
| | |
| | 23)SHT.P305-RISER S/3-SHALL COMPLY W/SPC |
| | SEC.911.3 & TABLE 911.3.(THIS CODE SEC. |
| | APPLIES TO ALL RISERS DESIGNED IN THE |
| | SAME MANNER.) |
| | |
| | 24)SHT,P305-RISERSS/5 & S/20-SHALL |
| | COMPLY W/SPC SEC.714.2.(APPLIES TO ALL |
| | RISERS OF THIS DESIGN.) |
| | |
| | 25)FIXTURES LOCATED ON STACKS ABOVE THE |
| | HIGHEST WATER CLOSET OR BATHTUB SHALL |
| | COMPLY W/SPC SEC.913.2.(SEE SHT.P306- |
| | RISER #S/6 AND ALL OTHERS OF THE SAME |
| | DESIGN.) |
| | |
| | 26)RELIEF VENTS ARE REQD.IN SOIL OR |
| | WASTE STACKS MORE THAN 10 BRANCH INTER- |
| | VALS PER SPC SEC.916 |
| | |
| | 27)OFFSET VENTS SHALL BE INSTALLED PER |
| | SPC 917.1,917.2,917.3.(SEE SHT.P306, |
| | RISERS S/11,S/25, AND ALL OTHER STACKS |
| | OF THE SAME DESIGN.) |
| | |
| | 28)SHT.P310-SHOW PIPE SIZES FOR THE |
| | GREASE WASTE AND SANITARY COLLECTION |
| | SYSTEMS.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | 29)SHT.P401-MIN.1"INSULATION IS REQD.ON |
| | C.W.PIPE AT WATER HEATER PER F.E.C. |
| | TABLE 4-11.(SEE NOTE #15.) |
| | |
| | 30)SUBMIT COMPLETE STORM DRAINAGE RISER |
| | FOR REVIEW.SHOW SQ.FT.AREA DRAINED BY |
| | EACH DRAIN,PIPE SIZES,SLOPE OF PIPE. |
| | INCLUDE ALL AREA DRAINS AND DECK DRAINS |
| | IN THE DRAWING.COUNTYWIDE AMENDMENTS TO |
| | SPC 104.2.1. |
| | |
| | 31)SUBMIT PROVISIONS,CALCULATIONS,AND |
| | DRAWINGS FOR SECONDARY DRAINAGE FOR THE |
| | ROOF.COMPLY W/SPC SECS.1109.1,1109.2, |
| | 1109.3 AND APPENDIX "A". |
| | |
| | 32)LAYOUT OF GREASY WASTE SYSTEM ON P310 |
| | DOESN'T CORRELATE W/P102.CLARIFY. |
| | |
| | 33)SHT.P310 NOTES 8"TO SANITARY AND |
| | P102 NOTES 6".CLARIFY.(SEE GREASE WASTE) |
| | |
| | 34)A PERMIT MAY BE REQD.FROM THE DEPT.OF |
| | ENVIRONMENTAL PROTECTION FOR THE WATER |
| | MAIN INSTALLATION.COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.101.4.7. |
| | |
| | 35)REQUIRED NUMBER OF SANITARY FIXTURES |
| | FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF |
| | HEALTH CHAPTER 64E-9.APPROVAL REQD.FROM |
| | HEALTH DEPT. |
| | |
| | 36)A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR THE FOUNTAIN. |
| | |
| | 37)SHT.P312-NOTES ALL P&T LINES AND DP |
| | LINES AS 1 1/2" AND P101 CALLS OUT |
| | 1 1/4".SHT.P101 ALSO NOTES 1 1/2" LINES |
| | DISCHARGING INTO A 1 1/4" LINE U/G AND |
| | A/G.CLARIFY.LINES SHALL NOT BE REDUCED |
| | IN SIZE PER VALVE MANUF.RECOMMENDATIONS. |