Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************DENIED********************
  
 1. ACCEPTANCE TEST FOR STAIRWAY PRESSUR-
 IZATIONPER NFPA 92A REQUIRED BY CERT-
 IFIED TEST AND BALANCE CONTRACTOR IN
 PRESSANCE OF CITY INSPECTORS
 2. ROOM W/ HP-1 IS RATED. ALL PENETRA-
 TIONS TO BE PROTECTED PER 1997 SMC 610
 1997 SMC 610.6 REQUIRES LOCATION AND
 INSTALLATION DETAILS TO BE SHOWN AND
 PROPERLY IDENTIFIED ON PLANS
 3.SHOW COMPLIANCE W/ SBC 412.5
 NOTE: OVERFLOW PROTECTION REQUIRED FOR
 ALL VERTICAL AND HORIZONTAL AHU AND HP
 PER 1997 SMC 304.8.6
 KITCHEN EXHAUST DUCT TO BE ACCESS-
 IBLE PER 1996 NFPA 96 4-3.4.3 EACH FLOOR
 IF NOT ACCESSIBLE THRU THE TOP BY PERSON
 NEL FOR CLEANING