| Plan Review Notes For Permit 00041269 |
| Permit Number |
00041269 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************DENIED******************** | | | | | | 1. ACCEPTANCE TEST FOR STAIRWAY PRESSUR- | | | IZATIONPER NFPA 92A REQUIRED BY CERT- | | | IFIED TEST AND BALANCE CONTRACTOR IN | | | PRESSANCE OF CITY INSPECTORS | | | 2. ROOM W/ HP-1 IS RATED. ALL PENETRA- | | | TIONS TO BE PROTECTED PER 1997 SMC 610 | | | 1997 SMC 610.6 REQUIRES LOCATION AND | | | INSTALLATION DETAILS TO BE SHOWN AND | | | PROPERLY IDENTIFIED ON PLANS | | | 3.SHOW COMPLIANCE W/ SBC 412.5 | | | NOTE: OVERFLOW PROTECTION REQUIRED FOR | | | ALL VERTICAL AND HORIZONTAL AHU AND HP | | | PER 1997 SMC 304.8.6 | | | KITCHEN EXHAUST DUCT TO BE ACCESS- | | | IBLE PER 1996 NFPA 96 4-3.4.3 EACH FLOOR | | | IF NOT ACCESSIBLE THRU THE TOP BY PERSON | | | NEL FOR CLEANING |
|