Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SHT.A110-THE NUMBER OF OCCUPANTS SHALL
 BE BASED ON HABITABLE FLOOR SPACE PER
 SPC TABLE 407.SEE SPC SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE FLOOR SPACE AND NOTE
 OCCUPANT LOAD ON PLANS.
  
 2)PLANS FOR POOL HOUSE SHALL BE REVIEWED
 BY PALM BEACH COUNTY HEALTH DEPT.PRIOR
 TO REVIEW BY THIS DEPT.SPC SEC.101.4.7.
  
 3)BATHROOMS IN THE DWELLING UNITS SHALL
 COMPLY W/THE FEDERAL FAIR HOUSING ACT 24
 CFR 100.205(C)(3)(I-IV).SUBMIT DETAILS
 OF REINFORCED WALLS FOR FUTURE INSTALL-
 ATION OF GRAB BARS.COMPLY W/FHA REQ.#6,
 FIGURES #3,4,& 5.
  
 4)CLEAR FLOOR SPACE FOR FIXTURES SHALL
 BE SHOWN ON THE PLAN AND DESIGNATE WHICH
 DESIGN SPECIFICATION("A"OR "B")OF THE
 FAIR HOUSING ACT IS BEING USED.
  
 5)SUBMIT HABITABLE SQUARE FOOT AREA OF
 EACH PUBLIC AND COMMON USE AREA TO
 DETERMINE OCCUPANT LOAD FOR MINIMUM
 SANITARY FACILITY REQS.COMPLY W/SPC
 TABLE 407.(RETAIL,EXERCISE,ETC.)
  
 6)SHT.A422-RESTROOM #R104 SHALL BE FULLY
 ACCESSIBLE PER FACBC SEC.4.1.3.(10)(A).
  
 7)SANITARY FACILITIES FOR THE RESTAURANT
 SHALL COMPLY W/FLA.STATUTE 553.141(3).
 (POTTY PARITY)
  
 8)CLEAR FLOOR SPACE FOR FIXTURES IN THE
 KITCHEN SHALL BE CENTERED ON THE FIXTURE
 PER FHA 24 CFR 100.205 REQ.#7(USABLE
 KITCHENS) AND FAIR HOUSING DESIGN MANUAL
  
 9)CLOSETS HOUSING WASHER/DRYER UNITS
 WHICH ARE INTENDED FOR PASSAGE SHALL
 HAVE 32" NOMINAL CLEAR OPENING PER FHA
 24 CFR 100.205 REQ.#7 & FHA DESIGN
 MANUAL.(SEE SHTS.A434 UNIT B3 AND SHT.
 A444 UNIT C7.)
  
 10)SHOW THE REQUIRED FIXTURE CLEARANCE
 DIMENSION OF THE WATER CLOSETS FROM
 FINISHED SURFACE OF ADJOINING WALLS,
 VANITIES,EDGE OF LAVATORY,OR ANY OTHER
 OBSTACLE PER FHA 24 CFR 100.205 REQ.#7.
  
 11)PUBLIC AND COMMON AREA TOILET ROOM
 SHALL HAVE WALLS AND FLOORS OF NONABSORB
 ENT MATERIAL TO HEIGHT OF 4'ABOVE THE
 FLOOR PER SBC 1204.2.NOTE ON SHT.A501.
  
 13)SHT-A601-SHOW MOUNTING HEIGHTS OF ALL
 HANDICAP FIXTURES AND CLEAR FLOOR SPACE
 BENEATH FIXTURES.COMPLY W/FACBC 1997 ED.
  
 14)SHT. A801-DETAIL#3 SHOWS 4"DIA.
 SCUPPER.SUBMIT CALCULATIONS FOR OVERFLOW
 DRAINAGE.COMPLY W/APPENDIX"A" OF SPC.
  
 15)SHT.FP101 ET.AL.-SHOWS DISCHARGE OF
 DRAINRISER TO STORM DRAINAGE SYSTEM.
 DISCHARGE SHALL BE TO EXTERIOR PER NFPA
 13 SEC.4-14.3.4.3.
  
 16)SHT.P101-CHECK KEYNOTES #10,11.
 LINE IS NOTED AS SANITARY AND CALLED OUT
 AS CONDENSATE AND RWL.
  
 17)SHT.P103-KEYNOTES #6 & 7 ARE
 MISLABELED.
  
 18)SUBMIT DETAIL OF OIL INTERCEPTOR.
 COMPLY W/CITY OF WEST PALM BEACH ENG.
 STANDARDS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 19)P200 DRAWINGS-CLEARLY LABEL RISERS
 FOR IDENTIFICATION AND REVIEW.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 20)VERTICAL COMBINATION WASTE AND VENT
 STACKS FOR KIT.SINKS SHALL COMPLY W/SPC
 SEC.911.4.(MAX.HEIGHT FOR 4"IS 100').
  
 21)SOIL AND WASTE STACKS SHALL REMAIN
 UNDIMINISHED IN SIZE FROM BUILDING DRAIN
 TO CONNECTION W/THE STACK VENT PER SPC
 SEC.714.2.
  
 22)SHT.P305-RISER #S/3-COMPLY W/SPC SEC.
 715.4.(THIS CODE SECTION APPLIES TO ALL
 RISERS DESIGNED IN THE SAME MANNER.)
 **SEE PLBG.STEP #2 FOR CONTINUATION*****