| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.A110-THE NUMBER OF OCCUPANTS SHALL |
| | BE BASED ON HABITABLE FLOOR SPACE PER |
| | SPC TABLE 407.SEE SPC SEC.407.1.3.FOR |
| | ALLOWED DEDUCTIBLE FLOOR SPACE AND NOTE |
| | OCCUPANT LOAD ON PLANS. |
| | |
| | 2)PLANS FOR POOL HOUSE SHALL BE REVIEWED |
| | BY PALM BEACH COUNTY HEALTH DEPT.PRIOR |
| | TO REVIEW BY THIS DEPT.SPC SEC.101.4.7. |
| | |
| | 3)BATHROOMS IN THE DWELLING UNITS SHALL |
| | COMPLY W/THE FEDERAL FAIR HOUSING ACT 24 |
| | CFR 100.205(C)(3)(I-IV).SUBMIT DETAILS |
| | OF REINFORCED WALLS FOR FUTURE INSTALL- |
| | ATION OF GRAB BARS.COMPLY W/FHA REQ.#6, |
| | FIGURES #3,4,& 5. |
| | |
| | 4)CLEAR FLOOR SPACE FOR FIXTURES SHALL |
| | BE SHOWN ON THE PLAN AND DESIGNATE WHICH |
| | DESIGN SPECIFICATION("A"OR "B")OF THE |
| | FAIR HOUSING ACT IS BEING USED. |
| | |
| | 5)SUBMIT HABITABLE SQUARE FOOT AREA OF |
| | EACH PUBLIC AND COMMON USE AREA TO |
| | DETERMINE OCCUPANT LOAD FOR MINIMUM |
| | SANITARY FACILITY REQS.COMPLY W/SPC |
| | TABLE 407.(RETAIL,EXERCISE,ETC.) |
| | |
| | 6)SHT.A422-RESTROOM #R104 SHALL BE FULLY |
| | ACCESSIBLE PER FACBC SEC.4.1.3.(10)(A). |
| | |
| | 7)SANITARY FACILITIES FOR THE RESTAURANT |
| | SHALL COMPLY W/FLA.STATUTE 553.141(3). |
| | (POTTY PARITY) |
| | |
| | 8)CLEAR FLOOR SPACE FOR FIXTURES IN THE |
| | KITCHEN SHALL BE CENTERED ON THE FIXTURE |
| | PER FHA 24 CFR 100.205 REQ.#7(USABLE |
| | KITCHENS) AND FAIR HOUSING DESIGN MANUAL |
| | |
| | 9)CLOSETS HOUSING WASHER/DRYER UNITS |
| | WHICH ARE INTENDED FOR PASSAGE SHALL |
| | HAVE 32" NOMINAL CLEAR OPENING PER FHA |
| | 24 CFR 100.205 REQ.#7 & FHA DESIGN |
| | MANUAL.(SEE SHTS.A434 UNIT B3 AND SHT. |
| | A444 UNIT C7.) |
| | |
| | 10)SHOW THE REQUIRED FIXTURE CLEARANCE |
| | DIMENSION OF THE WATER CLOSETS FROM |
| | FINISHED SURFACE OF ADJOINING WALLS, |
| | VANITIES,EDGE OF LAVATORY,OR ANY OTHER |
| | OBSTACLE PER FHA 24 CFR 100.205 REQ.#7. |
| | |
| | 11)PUBLIC AND COMMON AREA TOILET ROOM |
| | SHALL HAVE WALLS AND FLOORS OF NONABSORB |
| | ENT MATERIAL TO HEIGHT OF 4'ABOVE THE |
| | FLOOR PER SBC 1204.2.NOTE ON SHT.A501. |
| | |
| | 13)SHT-A601-SHOW MOUNTING HEIGHTS OF ALL |
| | HANDICAP FIXTURES AND CLEAR FLOOR SPACE |
| | BENEATH FIXTURES.COMPLY W/FACBC 1997 ED. |
| | |
| | 14)SHT. A801-DETAIL#3 SHOWS 4"DIA. |
| | SCUPPER.SUBMIT CALCULATIONS FOR OVERFLOW |
| | DRAINAGE.COMPLY W/APPENDIX"A" OF SPC. |
| | |
| | 15)SHT.FP101 ET.AL.-SHOWS DISCHARGE OF |
| | DRAINRISER TO STORM DRAINAGE SYSTEM. |
| | DISCHARGE SHALL BE TO EXTERIOR PER NFPA |
| | 13 SEC.4-14.3.4.3. |
| | |
| | 16)SHT.P101-CHECK KEYNOTES #10,11. |
| | LINE IS NOTED AS SANITARY AND CALLED OUT |
| | AS CONDENSATE AND RWL. |
| | |
| | 17)SHT.P103-KEYNOTES #6 & 7 ARE |
| | MISLABELED. |
| | |
| | 18)SUBMIT DETAIL OF OIL INTERCEPTOR. |
| | COMPLY W/CITY OF WEST PALM BEACH ENG. |
| | STANDARDS.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.101.4.7. |
| | |
| | 19)P200 DRAWINGS-CLEARLY LABEL RISERS |
| | FOR IDENTIFICATION AND REVIEW.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 20)VERTICAL COMBINATION WASTE AND VENT |
| | STACKS FOR KIT.SINKS SHALL COMPLY W/SPC |
| | SEC.911.4.(MAX.HEIGHT FOR 4"IS 100'). |
| | |
| | 21)SOIL AND WASTE STACKS SHALL REMAIN |
| | UNDIMINISHED IN SIZE FROM BUILDING DRAIN |
| | TO CONNECTION W/THE STACK VENT PER SPC |
| | SEC.714.2. |
| | |
| | 22)SHT.P305-RISER #S/3-COMPLY W/SPC SEC. |
| | 715.4.(THIS CODE SECTION APPLIES TO ALL |
| | RISERS DESIGNED IN THE SAME MANNER.) |
| | **SEE PLBG.STEP #2 FOR CONTINUATION***** |