Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) PROVIDE SEQUENCE OF OPERATION FOR
 STAIRWAY PRESSURIZATION. NOTE:
 ACCEPTANCE TEST PER NFPA 92A REQUIRED
 BY CERTIFIED TEST AND BALANCE COMPANY IN
 PRESSENCE OF CITY INSPECTORS
 2) M101 SHOW RETURN AIR PATH FOR HP-1
 20 MIN. RATED DOOR, NO FIRE DAMPER SHOWN
 AT DUCT LEAVING ROOM WITH HP-1
 3) M101 DUCT PENETRATING VALET ROOM WALL
 TO HAVE FIRE DAMPER AT PENETRATION IF
 WALL IS RATED (DOOR IS RATED TO ROOM)
 4) SHOW AIR BALANCE SCHEDULE AND AIR
 EXCHANGE CALCULATIONS FOR GARAGE AS
 REQUIRED BY CODE
 5) M102 NO FIRE DAMPER SHOWN AT DUCT
 PENETRATION OF ELEVATOR VESTIBULE AREA
 6) M107 ALL CHWSR RISERS IN GARAGE TO
 PROTECTED FROM DAMAGE
 7) PROVIDE SPECS FOR DRYER BOOSTER FANS
 8) DRYER EXHAUST DUCT TO BE RUN AS
 STRAIGHT AS POSSIBLE TO LIMIT 90 AND 45
 DEGREE BENDS
 9) SEVERAL BATH EXHAUST FANS (EF-A) HAVE
 NO DUCT SHOWN ATTACHED 1997 SMC 501.3
 REQUIRES ALL EXHAUSTED AIR TO BE DIS-
 CHARGED OUTDOORS
 10) NO DUCT RUNS SHOWN FOR LOFT DRYERS,
 PROVIDE INFORMATION ON PLAN
 11) PROVIDE RATING/SPECS ON HOSES FOR
 HEAT PUMPS
 12) OVERFLOW PROTECTION REQUIRED FOR ALL
 AHU AND HP (VERTICAL OR HORIZONTAL) PER
 1997 SMC 304.8.6
 13) PROVIDE INFORMATION WHERE AUX DRAIN
 TERMINATES (NOT FOUND ON PLUMBING PLANS)
 1997 SMC REQUIRES AUX DRAIN LINE TO TERM
 INATE IN A CONSPICUOUS LOCATION TO SERVE
 AS AN ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED
 14) PROVIDE INFORMATION ON LOCATION OF
 EXHAUST DUCT AND FAN LOCATION FOR FUTURE
 KITCHEN HOODS