Plan Review Notes
Plan Review Notes For Permit 00041269
Permit Number 00041269
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) KNOX-BOX NEEDED FOR FIRE RESCUE
 ACCESS.
 2) NO HYDRAULIC CALCULATIONS SHOWN FOR
 FIRE SPRINKLER SYSTEM DRAWINGS.
 3) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL VERTICAL SHAFTS,ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS.
 4) STANDPIPE SYSTEMS TO COVER ALL AREAS
 OF THE BUILDINGS WITH 100 FEET OF HOSE
 WITH 30 FEET OF NOZZLE SPRAY.
 5) EMERGENCY LIGHTING NEEDED IN FIRE
 PUMP ROOM.
 6) LOFTS NEED SMOKE DETECTORS ON EACH
 LEVEL.
 7) PROVIDE COMPLETE SHOP DRAWINGS ON THE
 FIRE ALARM SYSTEM. CUT SHEETS NEEDED ON
 ALL DEVICES PLANNED. SYSTEM TO BE CLASS
 A OR ADDRESSABLE. SYSTEM TO BE MONITORED
 BY A UL LISTED CENTRAL STATION.
 8) ADDRESS NOT SHOWN ON ELEVATION
 DRAWINGS.
 9) CANVAS AWNINGS TO BE FIRE RATED.
 10) FIRE SEPARATION BETWEEN GARAGE AND
 BUILDING TO BE AT LEAST 2 HOUR FIRE
 RATED.
 11) OPENINGS IN THIS TWO HOUR SEPARATION
 SHALL BE AT LEAST 1 1/2 RATED.
 12) GARAGE MECHANICAL VENTILATION TO
 PROVIDE AT LEAST SIX AIR CHANGES PER
 HOUR.
 13) PARKING GARAGE TO COMPLY WITH NFPA
 88A.
 14) KITCHEN EXHAUST SHAFTS TO MEET
 APPLICABLE FIRE RATINGS.
 15) STAIRS TO COMPLY WITH NEW STAIRS AS
 PER THE LIFE SAFETY CODE, 1985 EDITION.
 16) DOORS OPENING INTO CORRIDORS SHALL
 NOT ENTER MORE THAN SEVEN INCHES. CHECK
 ELECTRICAL CLOSETS.
 17) FIRE DAMPERS TO COMPLY WITH UL 555.
 18) KITCHEN HOOD, DUCT AND EXTINGUISHING
 SYSTEMS TO COMPLY WITH NFPA 96 AND 17A.
 19) ELEVATORS TO COMPLY WITH STANDARD
 BUILDING CODE 1997 EDITION SECTION
 3003.4, STRETCHER REQUIREMENTS.
 20) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, 1985 EDITION.
 21) ANY ASSEMBLY OCCUPANCY SPACE TO
 HAVE PROVISIONS FOR AT LEAST TWO
 PERSONS.
 22) PANIC HARDWARE ON RATED DOORS TO
 BE FIRE EXIT PANIC HARDWARE.
 23) ELEVATOR RECALL REQUIRED, SEE NOTE
 24) EXPLAIN NOTE ABOUT ASTRAGALS FOR
 DOUBLE RATED FIRE DOORS.