| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE:NEED TO SHOW THE REQ`D SMOKE | | | DETECTORS OUTSIDE BEDROOMS IN THE IMMED- | | | IATE VICINITY. THEY ARE ALSO REQ`D ON | | | EACH LEVEL IN COMMON AREAS. AS REQ`D BY | | | NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE:MISSING THE REQ`D OUTLET FOR | | | FRONT OF DWELLING PER 210-52E | | | | | | 3)NOTE:MISSING OUTLET FOR DOWNSTAIRS | | | BEDROOM PER 210-52 2` OF WALL | | | | | | 4)NOTE; OUTLET FOR GARAGE MUST BE GFI | | | AS PER 210-8 | | | | | | 5)NOTE:PLEASE SHOW THE REQ`D BATH(S) | | | CIRCUIT(S) AS PER 210-11-C-3.MUST BE | | | 20AMP AND #12 AWG. | | | | | | 6)NOTE:PLEASE SHOW THE GROUNDING ELEC- | | | -TRODE CONDUCTOR GOING TO COLD WATER | | | PIPE AND AND BLDG. STEEL AS REQ`D BY | | | 250-50 | | | | | | 7)NOTE:PLEASE PROVIDE THE AIC RATING OF | | | MAIN ON PANEL AND BRKRS. MAIN MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | AS PER 110-9. | | | | | | PLEASE NOTE THAT PLANS WOULD HAVE PASSED | | | WITH A PROVISO BUT WERE COMING BACK FOR | | | MECHANICAL BEING DENIED ANYWAY. PLEASE | | | MAKE THE ABOVE CHANGESAND SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|