2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT M04,6" CONDENSATE DRAIN, CLEAR
 WASTE ONLY,RERQUIRES A HUB DRAIN 1"
 ABOVE FF IN AEACH MECHANICAL ROOM.
 (2) CAP ON TOP OF 6" CONDENSATE RISER
 TO BE PERFORATED FOR VENTING.
 (3) PVC PIPE EXPOSED TO UV RAYS TO BE
 PROTECTED AS PER MANFACTURES
 RECOMENDATIONS.
 (4) SUPPORT PVC PIPE PER SPC 94 SEC 310.
 END OF COMMENTS