| Plan Review Notes For Permit 00041035 |
| Permit Number |
00041035 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | PROJECT RECIEVED FOR ENG REVIEW 6/1/00 | | | | | | REVIEW COMMENTS FOR SHEET C-2 | | | | | | 1. DIRECT TAPS MUST BE CALLED OUT | | | SPECIFIYING SIZE AND INSTALLATION BY | | | CONTRACTOR. (NO SADDLE TAPS ALLOWED) | | | | | | 2. REDUCE PREASSURE ASSEMBLIES MUST BE | | | INSTALLED AS MARKED ON PLAN. | | | | | | 3. BACKFLOWS MUST BE INSTALLED IN THE | | | PROPERTY JUST INSIDE THE R.O.W. LINE. | | | | | | 4. METERS MUST BE INSTALLED JUST OUSIDE | | | OF THE R.O.W. | | | | | | 5. VERTICAL CLEARANCES MUST BE CALLED | | | OUT BETWEEN WATER AND SEWER. AN 18" | | | MINIMUM CLEARANCE IS REQUIRED. | | | | | | 6. MUST HAVE ON PLAN "SUNSHINE" LOCATING | | | SERVICE NOTE ALONG WITH THE TELEPHONE | | | NUMBER 1 800 432 4770. | | | | | | 7. SUPPLY STANDARD UTILITY DETAIL | | | DRAWINGS TO CONTRACTOR. THIS APPLY'S | | | TO SERVICES, BACKFLOW, CLEAN-OUTS, | | | AND LATERALS ETC. | | | | | | 8. SUBMITSHOP DRAWINGS TO PROJECT | | | COORDINATOR FOR WATER SERVICES AND STORM |
|